3–18

“A” Group: Standard Functions

PID Control

When enabled, the built-in PID loop calculates an ideal inverter output value to cause a loop feedback process variable (PV) to move closer in value to the setpoint (SP). The current frequency command serves as the SP. The PID loop algorithm will read the analog input for the process variable (you specify the current or voltage input) and calculate the output.

A scale factor in A_75 lets you multiply the PV by a factor, converting it into engineering units for the process.

Proportional, integral, and derivative gains are all adjustable.

See “PID Loop Operation” on page 4–32 for more information.

 

 

 

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

Edit

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_71

PID Enable

 

Enables PID function,

00

00

00

 

 

 

 

 

two option codes:

 

 

 

 

 

 

 

 

PID SW

OFF

 

 

 

 

 

 

 

 

00 ...PID Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 ...PID Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring ParametersDrive

 

A_72

PID proportional gain

Proportional gain has a range

1.0

1.0

1.0

 

 

 

 

of 0.2 to 5.0

 

 

 

 

 

 

 

 

PID P

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_73

PID integral time

Integral time constant has a

1.0

1.0

1.0

sec.

 

 

 

constant

 

range of 0.0 to 150 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID I

001.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_74

PID derivative time

Derivative time constant has a

0.0

0.0

0.0

sec.

 

 

 

constant

 

range of 0.0 to 100 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID D

00.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_75

PV scale conversion

Process Variable (PV) scale

1.00

1.00

1.00

 

 

 

 

 

factor (multiplier), range of

 

 

 

 

 

 

 

 

PID CONV

01.00

 

 

 

 

 

 

 

 

0.01 to 99.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_76

PV source setting

Selects source of Process

00

00

00

 

 

 

 

 

Variable (PV), option codes:

 

 

 

 

 

 

 

 

PID INPT

CUR

 

 

 

 

 

 

 

 

00 ...[OI] terminal (current in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 ...[O] terminal (voltage in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The setting A_73 for the integrator is the integrator’s time constant Ti, not the gain. The integrator gain Ki = 1/Ti. When you set A_73 = 0, the integrator is disabled.