Using Intelligent Input Terminals
Operations and Monitoring
When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters the
In the figure below, parameter B_88 selects whether the inverter resumes operation from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS] terminal turns OFF. The application determines the best setting.
Parameter B_03 specifies a delay time before resuming operation from a
|
|
|
|
|
|
| B_88 = 00 |
| Resume from motor speed | B_88 = 01 |
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| wait time | |||||||||||||
Motor |
|
| Motor |
|
|
|
|
|
|
|
|
| B 03 | |||||||||||||||
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
speed | 1 |
|
|
|
|
|
|
|
|
|
| speed | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FRS |
|
|
|
|
|
|
|
|
|
| FRS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
0 |
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
[FW], | 1 |
|
|
|
|
|
|
|
|
|
| [FW], | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
[RV] | 0 |
|
|
|
|
|
|
|
|
|
| [RV] | 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
| t |
|
|
|
|
|
|
|
|
|
|
|
| t | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Option | Terminal | Function Name | Input |
|
|
| Description |
|
|
|
| |||
Code | Symbol | State |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
11 | FRS | ON | Causes output to turn OFF, allowing motor to | |||||||||||
|
|
|
| free run (coast) to stop |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| OFF | Output operates normally, so controlled deceler- | ||||||||||
|
|
|
| ation stops motor |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C_01, C_02, C_03, C_04, | Example (requires input configuration— | ||||||||||||
C_05 |
| |||||||||||||
|
|
| see page |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||
Required settings: | B_03, B_88, C_11 to C_15 |
|
|
|
|
| FRS |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Notes: |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| L |
| 5 | 4 | 3 |
| 2 | 1 | P24 |
| |
• When you want the [FRS] terminal to be active low |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
(normally closed logic), change the setting (C_11 to C_15) that corresponds to the input (C_01 to C_05) that is assigned the [FRS] function.
See I/O specs on page