3–23

L100 Inverter

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

 

Edit

 

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_01

Selection of restart

Select inverter restart method,

00

00

00

 

 

 

 

mode

 

four option codes:

 

 

 

 

 

 

 

 

 

 

 

00 ...Alarm output after trip,

 

 

 

 

 

 

 

 

 

IPS POWR

ALM

 

 

 

 

 

 

 

 

 

no automatic restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 ...Restart at 0Hz

 

 

 

 

 

 

 

 

 

 

 

02 ...Resume operation after

 

 

 

 

 

 

 

 

 

 

 

frequency matching

 

 

 

 

 

 

 

 

 

 

 

03 ...Resume previous freq.

 

 

 

 

 

 

 

 

 

 

 

after freq. matching, then

 

 

 

 

 

 

 

 

 

 

 

decelerate to stop and display

 

 

 

 

 

 

 

 

 

 

 

trip info.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_02

Allowable under-

The amount of time a power

1.0

1.0

1.0

sec.

 

 

 

 

voltage power failure

input under-voltage can occur

 

 

 

 

 

 

 

 

 

time

 

without tripping the power

 

 

 

 

 

 

 

 

 

 

 

failure alarm. Range is 0.3 to

 

 

 

 

 

 

 

 

 

IPS UVTIME 01.0s

 

 

 

 

 

 

 

 

 

25 sec. If under-voltage exists

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

longer than this time, the

 

 

 

 

 

 

 

 

 

 

 

inverter trips, even if the restart

 

 

 

 

 

 

ParametersDrive

 

 

 

 

mode is selected.

 

 

 

 

 

 

Configuring

 

 

 

 

 

 

 

 

 

 

B_03

Retry wait time before

Time delay after under-voltage

1.0

1.0

1.0

sec.

 

 

 

 

 

motor restart

 

condition goes away, before

 

 

 

 

 

 

 

 

 

 

 

the inverter runs motor again.

 

 

 

 

 

 

 

 

 

IPS WAIT

001.0s

 

 

 

 

 

 

 

 

 

Range is 0.3 to 100 seconds.