L100 Inverter
|
| “B” Function | Run |
| Defaults |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
Func. | Name / | Description | Mode | Units |
|
|
| ||||
Edit |
|
|
| ||||||||
Code | SRW Display | (CE) | (UL) | (Jpn) |
|
| |||||
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
B_01 | Selection of restart | Select inverter restart method, | ✘ | 00 | 00 | 00 | — |
|
|
| |
| mode |
| four option codes: |
|
|
|
|
|
|
|
|
|
|
| 00 ...Alarm output after trip, |
|
|
|
|
|
|
|
|
| IPS POWR | ALM |
|
|
|
|
|
|
|
| |
| no automatic restart |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 01 ...Restart at 0Hz |
|
|
|
|
|
|
|
|
|
|
| 02 ...Resume operation after |
|
|
|
|
|
|
|
|
|
|
| frequency matching |
|
|
|
|
|
|
|
|
|
|
| 03 ...Resume previous freq. |
|
|
|
|
|
|
|
|
|
|
| after freq. matching, then |
|
|
|
|
|
|
|
|
|
|
| decelerate to stop and display |
|
|
|
|
|
|
|
|
|
|
| trip info. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
B_02 | Allowable under- | The amount of time a power | ✘ | 1.0 | 1.0 | 1.0 | sec. |
|
|
| |
| voltage power failure | input |
|
|
|
|
|
|
|
| |
| time |
| without tripping the power |
|
|
|
|
|
|
|
|
|
|
| failure alarm. Range is 0.3 to |
|
|
|
|
|
|
|
|
| IPS UVTIME 01.0s |
|
|
|
|
|
|
|
| ||
| 25 sec. If |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
| longer than this time, the |
|
|
|
|
|
|
|
|
|
|
| inverter trips, even if the restart |
|
|
|
|
|
| ParametersDrive |
|
|
|
| mode is selected. |
|
|
|
|
|
| Configuring | |
|
|
|
|
|
|
|
|
|
| ||
B_03 | Retry wait time before | Time delay after | ✘ | 1.0 | 1.0 | 1.0 | sec. |
| |||
|
|
| |||||||||
| motor restart |
| condition goes away, before |
|
|
|
|
|
|
|
|
|
|
| the inverter runs motor again. |
|
|
|
|
|
|
|
|
| IPS WAIT | 001.0s |
|
|
|
|
|
|
|
| |
| Range is 0.3 to 100 seconds. |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|