“B” Group: Fine Tuning Functions
Electronic Thermal Overload Alarm SettingThe thermal overload detection protects the inverter and motor from overheating due to an excessive load. It uses a current/inverse time curve to determine the trip point.
First, use B_13 to select the torque characteristic that matches your load. This allows the inverter to utilize the best thermal overload characteristic for your application.
Torque
100%
80%
60%
0 | Hz |
120 |
The torque developed in a motor is directly proportional to the current in the windings,
which is also proportional to the heat generated (and temperature, over time). Therefore, you must set the thermal overload threshold in terms of current (amperes) for parameter B_12. The range is 50% to 120% of the rated current for each inverter model. If the current exceeds the level you specify, the inverter will trip and log an event (error E05) in the history table. The inverter turns the motor output OFF when tripped.
|
|
| “B” Function | Run |
| Defaults |
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
| Func. | Name / |
| Description | Mode |
| Units | |||
Configuring ParametersDrive |
|
| Edit |
| |||||||
| Code | SRW Display | (CE) | (UL) |
| (Jpn) | |||||
|
|
|
|
| |||||||
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |||
|
| B_12 | Level of electronic |
| Set a level between 50% and | ✘ | Rated current for each | % | |||
|
|
| thermal setting |
| 120% for the rated inverter |
| inverter model |
| |||
|
|
|
|
| current. |
|
| *See note |
|
| |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| B_13 | Electronic thermal |
| Select from two curves, option | ✘ | 01 | 01 |
| 00 | — |
|
|
| characteristic |
| codes: |
|
|
|
|
|
|
|
|
|
|
| 00 ...Reduced torque |
|
|
|
|
|
|
|
|
| CRT |
|
|
|
|
|
| ||
|
|
| 01 ...Constant torque |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WARNING: When parameter B_12, level of electronic thermal setting, is set to device FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor overload protection at 115% of device FLA or equivalent. Parameter B_12, level of electronic thermal setting, is a variable parameter.
NOTE: For inverter models 005NFE, 011NFE, and 030HFE, the thermal value is less than the rated amperes (is the same as models 004NFE, 007NFE, and 040HFE respec- tively). Therefore, be sure to set the electronic thermal overload according to the actual motor driven by the particular inverter.