L100 Inverter
Terminal Tightening Torque and Wire Sizexiii
The wire size range and tightening torque for field wiring terminals are presented in the table below.
Input | Motor Output | Inverter Model | Wiring Size | Torque | |||
|
|
|
| ||||
Voltage | kW | HP | Range (AWG) | ||||
| |||||||
|
|
| |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
| 0.2 | 1/4 |
| 0.6 | 0.8 | ||
|
|
|
|
| |||
| 0.4 | 1/2 | 16 | ||||
|
|
| |||||
|
|
|
|
|
|
| |
| 0.55 | 3/4 |
|
|
| ||
|
|
|
|
|
|
| |
| 0.75 | 1 | 14 |
|
| ||
|
|
|
|
|
| ||
200V | 1.1 | 1 1/2 | 0.9 | 1.2 | |||
| |||||||
|
|
|
| ||||
1.5 | 2 | 12 | |||||
|
|
| |||||
|
|
|
|
|
|
| |
| 2.2 | 3 | 10 |
|
| ||
|
|
|
|
|
|
| |
| 3.7 | 5 | 12 |
|
| ||
|
|
|
|
|
|
| |
| 5.5 | 7 1/2 | 10 | 1.5 | 2.0 | ||
|
|
|
|
| |||
| 7.5 | 10 | 8 | ||||
|
|
| |||||
|
|
|
|
|
|
| |
| 0.4 | 1/2 |
|
|
| ||
|
|
|
|
|
|
| |
| 0.75 | 1 | 16 |
|
| ||
|
|
|
|
|
| ||
| 1.5 | 2 | 0.9 | 1.2 | |||
|
| ||||||
|
|
|
|
| |||
400V | 2.2 | 3 |
| ||||
|
|
| |||||
|
|
|
|
|
| ||
3.0 | 4 | 14 |
|
| |||
|
|
| |||||
|
|
|
|
|
| ||
| 4.0 | 5 |
|
| |||
|
|
|
| ||||
|
|
|
|
|
|
| |
| 5.5 | 7 1/2 | 12 | 1.5 | 2.0 | ||
|
|
|
| ||||
| 7.5 | 10 | |||||
|
|
|
| ||||
|
|
|
|
|
|
|
WARNING: Field wiring connections must be | Terminal (ring lug) | |||||||
made by a UL Listed and CSA Certified ring lug | ||||||||
| Cable support | |||||||
terminal connector sized for the wire gauge being |
| |||||||
|
|
|
|
|
|
| ||
used. The connector must be fixed using the |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
crimping tool specified by the connector |
|
|
|
|
|
|
| |
manufacturer. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
Cable