3–34

“C” Group: Intelligent Terminal Functions

Input Function Summary Table – This table shows all fifteen intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4–8.

 

 

 

 

Input Function Summary Table

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

FW

Forward Run/Stop

ON

Inverter is in Run Mode, motor runs forward

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

01

RV

Reverse Run/Stop

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

02

CF1

Multi-speed Select,

ON

Binary encoded speed select, Bit 0, logical 1

 

 

 

 

Bit 0 (LSB)

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 0, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

CF2

Multi-speed Select,

ON

Binary encoded speed select, Bit 1, logical 1

 

 

 

 

Bit 1

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 1, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

CF3

Multi-speed Select,

ON

Binary encoded speed select, Bit 2, logical 1

 

Configuring ParametersDrive

 

 

 

Bit 2

 

 

 

 

 

OFF

Binary encoded speed select, Bit 2, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

CF4

Multi-speed Select,

ON

Binary encoded speed select, Bit 3, logical 1

 

 

 

 

Bit 3 (MSB)

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 3, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

JG

Jogging

ON

Inverter is in Run Mode, output to motor runs at

 

 

 

 

 

 

jog parameter frequency

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode

 

 

 

 

 

 

 

 

 

09

2CH

2-stage Acceleration

ON

Frequency output uses 2nd-stage acceleration

 

 

 

 

and Deceleration

 

and deceleration values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Frequency output uses standard acceleration and

 

 

 

 

 

 

deceleration values

 

 

 

 

 

 

 

 

 

11

FRS

Free-run Stop

ON

Causes output to turn OFF, allowing motor to

 

 

 

 

 

 

free run (coast) to stop

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output operates normally, so controlled deceler-

 

 

 

 

 

 

ation stops motor

 

 

 

 

 

 

 

 

 

12

EXT

External Trip

ON

When assigned input transitions OFF to ON,

 

 

 

 

 

 

inverter latches trip event and displays E12

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No trip event for ON to OFF, any recorded trip

 

 

 

 

 

 

events remain in history until Reset

 

 

 

 

 

 

 

 

 

13

USP

Unattended Start

ON

On powerup, the inverter will not resume a Run

 

 

 

 

Protection

 

command (mostly used in the US)

 

 

 

 

 

 

 

 

 

 

 

 

OFF

On powerup, the inverter will resume a Run

 

 

 

 

 

 

command that was active before power loss