Component Descriptions
AC Reactors, Input SideThis is useful in suppressing harmonics induced on the power supply lines, or when the main power voltage imbalance exceeds 3% (and power source capacity is more than 500 kVA), or to smooth out line fluctuations. It also improves the power factor.
In the following cases for a
•If the unbalanced factor of the power supply is 3% or higher
•If the power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more)
•If abrupt power supply changes are expected
Examples of these situations include:
1.Several inverters are connected in parallel, sharing the same power bus
2.A thyristor converter and an inverter are connected in parallel, sharing the same power bus
3.An installed
Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an
VRS = 205V, VST = 203V, VTR = 197V,
where VRS is
Unbalance factor of voltage = | ⋅ 100 | |||||||
|
| Meanline voltage |
|
|
| |||
= | VRS – (VRS + VST + VTR) ⁄ 3 | ⋅ 100 = | 205 – 202 | ⋅ 100 = | 1.5% | |||
+ VST + VTR) ⁄ 3 | ||||||||
|
|
|
|
|
Please refer to the documentation that comes with the AC reactor for installation instruc- tions.
AC Reactors, Output SideThis reactor reduces the vibrations in the motor caused by the inverter’s switching waveforms, by smoothing the waveforms to approximate commercial power quality. It is also useful to reduce the reflected voltage wave phenomenon when wiring from the inverter to the motor is more than 10m in length. Please refer to the documentation that comes with the AC reactor for installation instructions.