Example Wiring Diagram

Specifications of Control and Logic Connections

The control logic connectors are located just behind the front panel half-door. The relay contacts are accessible behind the main door. Connector labeling is shown below.

Logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

5

 

4

3

2

1

P24

 

 

 

 

 

AL0

AL1

AL2

 

inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

O

 

OI

 

L

FM

CM2

12

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contacts

 

 

 

 

 

Analog

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

 

Logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inputs

 

output

outputs

 

 

 

 

 

 

Specifications for the logic connection terminals are in the following table:

 

 

Terminal Name

Description

Ratings

 

 

 

 

 

 

 

 

 

 

 

 

[P24]

+24V for logic inputs

24VDC, 30 mA max (do not short to terminal L)

 

 

 

 

 

 

 

[1], [2], [3], [4], [5]

Discrete logic inputs

27VDC max. (use P24 or an external supply refer-

 

 

 

 

enced to terminal L)

 

 

 

 

 

 

 

[L] (top row) *1

GND for logic inputs

sum of input 1-5 currents (return)

 

 

 

 

 

 

 

[11], [12]

Discrete logic outputs

50mA maximum ON state current,

Operations Monitoringand

 

 

 

27 VDC maximum OFF state voltage

 

 

 

 

 

[CM2]

GND for logic outputs

100 mA: sum of 11 and 12 currents (return)

 

 

 

 

 

 

 

 

 

[FM]

PWM (analog/digital) output

0 to 10VDC, 1 mA, PWM and 50% duty digital

 

 

 

 

 

 

 

[L] (bottom row) *1

GND for analog inputs

sum of OI, O, and H currents (return)

 

 

 

 

 

 

 

[OI]

Analog input, current

4 to 19.6 mA range, 20 mA nominal

 

 

 

 

 

 

 

[O]

Analog input, voltage

0 to 9.6 VDC range, 10VDC nominal,

 

 

 

 

input impedance 10 k

 

 

 

 

 

 

 

[H]

+10V analog reference

10VDC nominal, 10 mA max

 

 

 

 

 

 

 

 

[AL0]

Relay common contact

250 VAC, 2.5A (R load) max.,

 

 

 

 

250 VAC, 0.2A (I load, P.F=0.4) max.

 

 

[AL1]

Relay contact, normally

 

 

100 VAC, 10mA min.

 

 

 

closed during RUN

 

 

 

30 VDC, 3.0A (R load) max.

 

 

 

 

 

 

[AL2]

Relay contact, normally open

30 VDC, 0.7A (I load, P.F.=0.4) max.

 

 

 

during RUN

5 VDC, 100mA min.

 

 

 

 

 

Note 1: The two terminals [L] are electrically connected together inside the inverter.