3–3

L100 Inverter

Using Keypad Devices

Inverter Front Panel Keypad

The L100 Series inverter front keypad contains all the elements for both monitoring and programming parameters. The keypad layout is pictured below. All other programming devices for the inverter have a similar key arrangement and function.

Parameter Display

 

 

 

 

Power LED

Run/Stop LED

 

 

HITACHI

POWER

 

 

 

 

 

Display Units

 

 

 

 

 

PRG

5 0.0

A

 

 

 

RUN

 

Hz

 

Hertz / Amperes LEDs

Program/Monitor LED

 

 

 

 

 

 

 

 

 

 

 

Run Key Enable LED

 

RUN

STOP

 

 

Potentiometer Enable LED

 

RESET

MAX

 

 

Run Key

 

MIN

 

Potentiometer

FUNC.

1 2 STR

 

Stop/Reset Key

 

 

 

 

 

 

Up/Down keys

Store key

Function key

Key and Indicator Legend

Run/Stop LED - ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode).

Program/Monitor LED - This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode).

Run Key Enable LED - is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled.

Run Key - Press this key to run the motor (the Run Enable LED must be ON first). Parameter F_04, Keypad Run Key Routing, determines whether the Run key gener- ates a Run FWD or Run REV command.

Stop/Reset Key - Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped.

Potentiometer - Allows an operator to directly set the motor speed when the potenti- ometer is enabled for output frequency control.

Potentiometer Enable LED - ON when the potentiometer is enabled for value entry.

Parameter Display - A 4-digit, 7-segment display for parameters and function codes.

Display Units, Hertz/Amperes - One of these LEDs will be ON to indicate the units associated with the parameter display.

Power LED - This LED is ON when the power input to the inverter is ON.

Function Key - This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values.

Up/Down ( 1 , 2 ) Keys - Use these keys alternately to move up or down the lists of parameter and functions shown in the display, and increment/decrement values.

Store ( STR ) Key - When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM.

Parameters Drive

Configuring