L100 Inverter
Reset InverterThe [RS] terminal causes the inverter to |
|
|
|
|
|
|
|
|
| 12 ms |
| ||
execute the reset operation. If the inverter is |
| 1 |
|
|
|
|
|
| minimum |
| |||
in Trip Mode, the reset cancels the Trip state. | [RS] | 0 |
|
|
|
|
|
|
|
|
|
|
|
When the signal [RS] is turned ON and OFF, |
|
|
|
|
|
| approx. 30 ms |
| |||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
| ||||||||
the inverter executes the reset operation. The | Alarm | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
minimum pulse width for [RS] must be 12 ms | signal | 0 |
|
|
|
|
|
|
|
|
|
|
|
or greater. The alarm output will be cleared | t |
| |
within 30 ms after the onset of the Reset command. |
|
WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.
Option | Terminal | Function Name | Input |
|
| Description | |||||||||
Code | Symbol | State |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
18 | RS | Reset Inverter | ON | The motor output is turned OFF, the Trip Mode | |||||||||||
|
|
|
| is cleared (if it exists), and powerup reset is | |||||||||||
|
|
|
| applied | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| OFF | Normal | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Valid for inputs: | C_01, C_02, C_03, C_04, | Example (default input configuration | |||||||||||||
C_05 |
| ||||||||||||||
|
|
| |||||||||||||
|
|
|
| ||||||||||||
Required settings: | (none) |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| RS | |||||||||
Notes: |
|
|
| ||||||||||||
|
|
|
| L | 5 | 4 | 3 | 2 | 1 | P24 |
| ||||
• When the control terminal [RS] input is already ON |
|
| |||||||||||||
at powerup for more than 4 seconds, the remote |
|
|
|
|
|
|
|
|
|
|
| ||||
operator display is |
|
|
|
|
|
|
|
|
|
|
| ||||
display of the digital operator | – |
|
|
|
|
|
|
|
|
|
|
| |||
However, the inverter has no error. To clear the |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |||||
digital operator error, turn OFF the terminal [RS] |
|
|
|
|
|
|
|
|
|
|
| ||||
See I/O specs on page | |||||||||||||||
input and press one of the operator keys. |
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•Pressing the Stop/Reset key of the digital operator can generate a reset operation only when an alarm occurs.
•A terminal configured with the [RS] function can only be configured for normally open operation. The terminal cannot be used in the normally closed contact state.
•When input power is turned ON, the inverter performs the same reset operation as it does when a pulse on the [RS] terminal occurs.
•The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a
•If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).