3–39

L100 Inverter

Output Function Adjustment Parameters

The following parameters work in conjunction with the intelligent output function, when configured. The overload level parameter (C_41) sets the motor current level at which the overload signal [OL] turns ON. The range of settings is from 0% to 200% of the rated current for the inverter. This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).

Motor current

C 41

0

t

Overload signal 1

0

t

The frequency arrival signal, [FA1] or [FA2], is intended to indicate when the inverter output has reached (arrived at) the target frequency. You can adjust the timing of the leading and trailing edges of the

Output

frequency

C 42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C 43

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal via two parameters specific to acceleration and deceleration ramps, C_42 and C_43.

Arrival signal

1

0

t

The Error for the PID loop is the magnitude (absolute value) of the difference between the Setpoint (desired value) and Process Variable (actual value). The PID output deviation signal [OD] (output terminal function option code 04) indicates when the error magnitude has exceeded a magnitude you define.

PID Error (PV–SP) deviation threshold

PV

Output SP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

C 44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

Deviation sig-1

0

t

 

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

Edit

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_41

Overload level setting

Sets the overload signal level

Rated current for each

 

 

 

 

 

between 0% and 200% (from 0

 

 

inverter

 

 

 

 

 

OV Load

03.00A

 

 

 

 

 

 

 

to two times the rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the inverter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_42

Frequency arrival

Sets the frequency arrival

0.0

0.0

0.0

Hz

 

 

 

setting for acceleration

setting threshold for the output

 

 

 

 

 

 

 

 

 

 

frequency during acceleration

 

 

 

 

 

 

 

 

ARV ACC

000.0Hz