3745 Panel Codes

Table 1-5 (Page 28 of 33). Panel Codes. An

ñ
following a panel code denotes that the code should 'Blink'.
Panel
Code Definition Action: Go to “3745 FRU Group
Table” on page 1-49
or to MAP number
F08 Status/progression step which occurs during the IML
sequence; find directory entry Normal progression code. If this code
is displayed for more than 2 minutes,
then a MOSS microcode problem is
suspected. Contact your support
structure, refer to “Contacting
Support” on page A-1.
F09 Status/progression step which occurs during the IML
sequence; IML end - go to MOSS loader
F0A Status/progression step which occurs during the IML
sequence; Ram entry (Start of MOSS Init step 1)
F0B Status/progression step which occurs during the IML
sequence; end of MOSS init step 1
Normal progression code. If this code
is displayed during the 1st installation,
a manual intervention is required to
exchange the wrap block.
F0C Status/progression step which occurs during the IML
sequence; start of MOSS init step 2 (Moss level 7)
Normal progression code. If this code
is displayed for more than two
minutes, then suspect any adapters
attached to the MOSS, or microcode
problem is suspected. Contact your
support structure, refer to “Contacting
Support” on page A-1.
F0D Status/progression step which occurs during the IML
sequence; IML complete with errors detected during
MOSS diagnostics.
MOSS diagnostics detected an error
during the IML.
Normally a reference code will
have been produced on the 3745
console. Refer to “Using Refer-
ence Codes” on page 1-14.
This code may be caused by a
console problem which prevents
the display of the reference code.
If this is the case, go to “3745
Console Symptoms” on
page 1-10.
F0E Status/progression step which occurs during the IML
sequence; IML complete - MOSS ALONE N/A
F0F Status/progression step which occurs during the IML
sequence; IML Complete - CCU connected - MOSS
OFFLINE
If this code appear without requested
IML (MOSS become alone during
normal operations) look at the
console for messages and go to
“3745 Console Symptoms” on
page 1-10
F10 Errors detected during the IPL sequence; Solid error
during MIOC
operation A reference code will have been
produced on the 3745 console. Refer
to “Using Reference Codes” on
page 1-14.
F11 Errors detected during the IPL sequence; CCU
hardcheck during a CCU IPL in progress
F12 Errors detected during the IPL sequence; Host IPL
request during CCU IPL in progress
F13 Errors detected during the IPL sequence; Unidentified
IPL selection
F14 Errors detected during the IPL sequence; CDS not cor-
rectly built by the CDF
A reference code will have been
produced on the 3745 console. Refer
to “Using Reference Codes” on
page 1-14.
F15 Unused Go to “MAP 3220: Undefined Panel
Message” on page 2-5
F16 Errors detected during the IPL sequence; CCU memory
test failed
A reference code will have been
produced on the 3745 console. Refer
to “Using Reference Codes” on
page 1-14.
F17 Errors detected during the IPL sequence; CCU test
failed
If this code is displayed during IML:
1. Run IOC bus diagnostics to
ensure that there is no adapter
problem.
2. Run CCU diagnostics.
1-42 3745 Models 130 to 17A: MIP