3745 MAPs
MAP 3210: MOSS Control Panel Code 059
Symptom Explanation Conditions That Could Cause This Symptom
Code 059 displayed on control
panel MPC
MCC
DFA
001
This MAP should be used only if the problem can
be reproduced.
If you have an intermittent problem, exchange the
FRU group 1. Go to “3745 FRU Group Table” on
page 1-49.
Power the 3745 OFF as follows:
- Put the power control in local mode:
Using Power Control, scroll till
the value is 3.
Press Validate.
- Press Power Off.
Switch the CB1 OFF. Refer to
Figure 4-40 on page 4-34
Attention: Use the ESD kit and
procedures.
Refer to Figure 4-9 on page 4-11.
Unplug the DFA card (01A-X0G).
Attention: The following sequence
should always be observed.
Remove the cable which is attached to the
MCC card (01A-X0H).
Unplug the MCC card (01A-X0H).
Press Power On Reset.
Switch the CB1 ON.
Is code 07E displayed?
Yes No
002
Press Power Off.
Switch the CB1 OFF.
Replug all cards and reinstall the
cable on the MCC card.
Exchange the MPC card. Go to Step 006.
003
Press Power Off.
Switch the CB1 OFF.
Replug the MCC card (01A-X0H).
Install the cable to the MCC card
(01A-X0H).
Press Power On Reset.
Switch the CB1 ON.
(Step 003 continues)
003 (continued)
Is code 072 displayed?
Yes No
004
Press Power Off.
Switch the CB1 OFF.
Remove the cable which is attached
to the MCC card (01A-X0H).
Exchange the MCC card, install the cable
on the MCC card. Go to Step 006.
005
Press Power Off.
Switch the CB1 OFF.
Exchange the DFA card (01A-X0G). Continue
with Step 006.
006
Reinstall any remaining unplugged cards.
Press Power On Reset.
Switch the CB1 ON.
Is an error detected during IML?
Yes No
007
Go to “CE Leaving Procedure” on
page 4-102.
008
Is the panel code displaying the same code as
when you started this MAP?
Yes No
009
Go to “3745 Control Panel Codes” on
page 1-15 and follow the procedure given
by the table.
010
Go to “Contacting Support” on page A-1.