A: Technical Specifications and Pinouts

Environmental Specifications

Table A-4 lists the environmental specifications of the 42U rack system. Table A-5 provides the environmental information for the 20U system.

Table A-4

Environmental Specifications (42U Rack)

 

 

 

Feature

 

Specification

 

 

Temperature tolerance

+5 °C (41 °F) to +35 °C (95 °F) (up to 1500 m / 5000 ft.)

(operating)

 

+5 °C (41 °F) to +30 °C (86 °F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)

Temperature tolerance

-40 °C (-40 °F) to +60 °C (140 °F)

(non-operating)

 

 

Relative humidity

10% to 90% operating (no condensation)

 

 

8% to 95% non-operating (no condensation)

Heat dissipation

 

 

Altix 450 (42U rack)

59.71 kBTU/hr maximum (based on 17.5 kW)

Cooling requirement

Ambient air cooling

Air flow: intake (front),

Approximately 1400 CFM (normal operation)

exhaust (rear)

 

 

Maximum altitude

10,000 ft. (3,049 m) operating

 

 

40,000 ft. (12,195 m) non-operating

Acoustical noise level

Less than 65 dBa maximum (with doors)

 

 

 

.