7: Troubleshooting and Diagnostics

Table 7-2

L1 Controller Messages

(continued)

 

 

L1 System Controller Message

Message Meaning and Action Needed

Temperature messages: low alt.

ATTN: <temp sensor description> advisory temperature reached @ xxC xxF

ATTN: <temp sensor description> critical temperature reached @ xxC xxF

ATTN: <temp sensor description> fault temperature reached @ xxC xxF

Temperature messages: high alt.

The ambient temperature at the IRU’s air inlet has exceeded 30° C.

The ambient temperature at the IRU’s air inlet has exceeded 35 °C.

The ambient temperature at the IRU’s air inlet has exceeded 40 °C.

ATTN: <temp sensor description> advisory temperature reached @ xxC xxF

ATTN: <temp sensor description> critical temperature reached @ xxC xxF

ATTN: <temp sensor description> fault temperature reached @ xxC xxF

Temperature stable message:

The ambient temperature at the IRU’s air inlet has exceeded 27 °C.

The ambient temperature at the IRU’s air inlet has exceeded 31 °C.

The ambient temperature at the IRU’s air inlet has exceeded 35 °C.

ATTN: <temp sensor description> stabilized @ xxC/xxF

The ambient temperature at the IRU’s air inlet has returned to an acceptable level.

Power-off messages:

 

Auto power down in xx seconds

The L1 controller has registered a fault and is

 

shutting down. The message displays every five

 

seconds until shutdown.

IRU appears to have been powered down

The L1 controller has registered a fault and has shut

 

down.

 

 