1: System Installation

Installing the IRUs in a Rack

This section describes how to install the IRUs that compose an Altix 450 system in a rack. This section also describes how to remove the IRUs from a rack. You can use the instructions to rackmount one or more IRUs in a 20U (short) or 42U (tall) Altix rack.

Caution: Always use at least two people when moving, installing, or removing a rackmounted ! Altix 450 IRU.

This rackmounting information is found in the following sections:

• “Determining Space Requirements” on page 24

• “Determining Where to Attach Rails in a Rack” on page 25

• “Rackmounting IRUs with Shelf Rails” on page 26

Determining Space Requirements

Table 1-2 specifies the space requirements when rackmounting an IRU in a 19-inch rack.

Table 1-2

IRU Space Requirements

 

 

 

 

Height

 

(5U) 8.68 inches (22 cm)

Width

 

17.5 inches (44.45 cm)

Depth

 

32.5 inches (82.5 cm) with blower attached

Weight

 

~130 lb (59 kg) max configa

Required front clearance for IRU

8.25 in. (20.96 cm)

Required rear clearance for IRU

10 in. (25.40 cm)

Required side clearance for IRU

No clearance requirement

Required front clearance for rack

48 in. (122 cm)

Required rear clearance for rack

48 in. (122 cm)

a.Weight will vary slightly depending on the number of blades installed and the amount of DIMMs installed, and on whether you have one or two disk drives in the IRU.

24

007-4857-002

Page 46
Image 46
Intel SGI Altix 450 manual Installing the IRUs in a Rack, Determining Space Requirements