Router Environmental Specifications

Table 19 on page 173 specifies the environmental specifications required for normal router operation. In addition, the site should be as dust-free as possible. Dust can clog air intake vents, reducing cooling system efficiency. Check the vents frequently, cleaning them as necessary. For more information, see “Maintaining Hardware Components” on page 73.

Table 19: Router Environmental Specifications

Description

Value

Altitude

No performance degradation to 10,000 ft (3048 m)

Relative humidity

Normal operation ensured in relative humidity range of 5% to

 

90%, noncondensing

Temperature

Normal operation ensured in temperature range of 32°F (0°C) to

 

104°F (40°C)

 

Non-operating storage temperature in shipping crate: –40°F (–40°C)

 

to 158°F (70°C)

Seismic

Designed to meet Telcordia Technologies Zone 4 earthquake

 

requirements

Maximum thermal output

AC: 3276 BTU/hour (960 W)

 

DC: 1965 BTU/hour (576 W)

NOTE: Install the router only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.

For additional safety guidelines and requirements, see “Safety and Regulatory

Compliance Information” on page 135.