FIRE SIREN TIME

FIRE SIREN TIME

The factory-set fire siren time is five minutes (UL installation maximum).

STEP #32 The fire siren time can be adjusted from one to 30 minutes using this step.

PROGRAMMING STEP #32

ENTERS STEP NUMBER

TIME IN MINUTES 1 - 30

STORES VALUE - 1 BING

AUTOMATION OUTPUT TIME

The factory setting causes the Automation Output to toggle between on and off with each activation.

STEP #40 The Automation Output can be programmed to turn on, then automatically turn off after one to 2500 seconds (42 minutes), or toggle on & off, using this step.

PROGRAMMING STEP #40

ENTERS STEP NUMBER

TIME IN SECONDS 1 - 2500 0 = TOGGLE ON & OFF

STORES VALUE - 1 BING

REMOTE CONTROL & HARDWIRE ARMING LEVEL

The factory setting causes the portable remote controls to arm to the Away Mode.

STEP #50 The portable remote controls can be changed to

arm to the Home Mode using this step.

NOTE: Changing this setting will affect all the portable remote controls used with the system and all hardwired loops programmed as arm/disarm (sensor Function #9) key stations.

PROGRAMMING STEP #50

ENTERS STEP NUMBER

2 FOR HOME MODE

3 FOR AWAY MODE

STORES VALUE - 1 BING

REMOTE CONTROL & HARDWIRE DISARMING LEVEL

The factory setting causes the portable remote controls to disarm to the Off Mode.

STEP #51 The remote controls can be changed to disarm to the Chime Mode using this step.

NOTE: Changing this setting will affect all the portable remote controls used with the system and all hardwired loops programmed as arm/disarm (sensor Function #9) key stations.

PROGRAMMING STEP #51

ENTERS STEP NUMBER

0 FOR OFF MODE

1 FOR CHIME MODE

STORES VALUE - 1 BING

ENTRY DELAY BEEPS

The factory setting causes the keypad(s) to beep during Entry Delays.

STEP #61 The Entry Delay beeps can be silenced using this step.

With the Entry Delay beeps off, the keypad(s) will be silent after a delayed sensor is triggered until the Entry Delay expires, then the alarm siren will sound.

PROGRAMMING STEP #61

ENTERS STEP NUMBER

0 FOR ENTRY BEEPS OFF

1 FOR ENTRY BEEPS ON

STORES VALUE - 1 BING

EXIT DELAY BEEPS

The factory setting causes the keypad(s) to beep during Exit Delays.

STEP #62 The Exit Delay beeps can be silenced using this step.

With the Exit Delay beeps off, the keypad(s) will be silent after arming to the Away Mode until the Exit Delay expires, then a single “Gong” tone will sound.

PROGRAMMING STEP #62

ENTERS STEP NUMBER

0 FOR EXIT BEEPS OFF

1 FOR EXIT BEEPS ON

STORES VALUE - 1 BING