03_NVspec_ver304e

3.SNVT Table

3-1.The network variables for individual operation/monitoring.

 

 

 

 

 

 

Model

 

 

nv No.

 

 

 

 

 

 

 

 

Name (*1)

 

I/O

CITY

 

LOSSNAY

Page.

(*1)

 

Mr.SLIM

 

 

 

 

 

 

MULTI

interlocks with

operation from

 

 

 

 

 

 

 

the indoor unit

LonWorks

 

 

 

 

 

 

 

 

 

 

1n

Request On/Off

nviOnOff_n

IN

(*9)

14

SNVT_switch

 

 

 

 

 

 

 

 

2n

On/Off run state

nvoOnOff_n

OUT

(*9)

14

SNVT_switch

 

 

 

 

 

 

 

 

3n

Request Mode

nviMode_n

IN

(*6)

(*6)

 

 

15

SNVT_hvac_mode

 

 

 

 

 

 

 

 

 

 

4n

Mode state

nvoMode_n

OUT

 

 

15

SNVT_hvac_mode

 

 

 

 

 

 

 

 

 

 

5n

SetPoint

nviSetP_n

IN

(*6)

(*6)

 

 

16

SNVT_temp_p

 

 

 

 

 

 

 

 

 

 

6n

SetPoint state

nvoSetP_n

OUT

(*5)

(*5)

 

 

16

SNVT_temp_p

 

 

 

 

 

 

 

 

 

 

7n

Request LOSSNAY Mode

nviLCMode_n

IN

 

 

 

(*3)

17

SNVT_switch

 

 

 

 

 

 

 

 

 

 

 

8n

LOSSNAY Mode state

nvoLCMode_n

OUT

 

 

 

(*3)

17

SNVT_switch

 

 

 

 

 

 

 

 

 

 

 

9n

Request Fanspeed

nviFanSpeed_n

IN

(*6)

(*6)

 

(*6)

18

SNVT_switch

 

 

 

 

 

 

 

 

 

10n

FanSpeed state

nvoFanSpeed_n

OUT

(*6)

(*6)

 

(*6)

18

SNVT_switch

 

 

 

 

 

 

 

 

 

11n

Request Local Prohibit On/Off

nvoProOnOff_n

IN

(*7,8)

(*7)

 

(*7)

19

SNVT_switch

 

 

 

 

 

 

 

 

 

12n

Local Prohibit On/Off state

nvoProOnOff_n

OUT

(*7,8)

(*7)

 

(*7)

19

SNVT_switch

 

 

 

 

 

 

 

 

 

13n

Request Local Prohibit Mode

nviProMode_n

IN

(*7,8)

(*7)

 

 

20

SNVT_switch

 

 

 

 

 

 

 

 

 

 

14n

Local Prohibit Mode state

nvoProMode_n

OUT

(*7,8)

(*7)

 

 

20

SNVT_switch

 

 

 

 

 

 

 

 

 

 

15n

Request Local Prohibit SetPoint

nviProSetP_n

IN

(*7,8)

(*7)

 

 

21

SNVT_switch

 

 

 

 

 

 

 

 

 

 

16n

Local Prohibit SetPoint state

nvoProSetP_n

OUT

(*7,8)

(*7)

 

 

21

SNVT_switch

 

 

 

 

 

 

 

 

 

 

17n

Request Forced Thermostat OFF

nviThermoOff_n

IN

 

 

22

SNVT_switch

 

 

 

 

 

 

 

 

 

 

18n

Forced Thermostat OFF state

nvoThermoOff_n

OUT

 

 

22

SNVT_switch

 

 

 

 

 

 

 

 

 

 

19n

Filter Sign Reset

nviFiltReset_n

IN

 

23

SNVT_switch

 

 

 

 

 

 

 

 

 

20n

Filter Run Time

nvoOnTime_n

OUT

 

 

23

SNVT_time_hour

 

 

 

 

 

 

 

 

 

 

21n

Space Temperature

nvoSpaceTemp_n

OUT

 

 

24

SNVT_temp_p

 

 

 

 

 

 

 

 

 

 

22n

Alarm state

nvoAlarm_n

OUT

(*2)

(*2)

(*2)

(*2)

25

SNVT_switch

 

 

 

 

 

 

 

 

23n

Error Code

nvoErrCode_n

OUT

(*2)

(*2)

(*2)

(*2)

25

SNVT_count

 

 

 

 

 

 

 

 

24n

Error Unit Address

nvoErrAdrs_n

OUT

(*2)

(*2)

(*2)

(*2)

26

SNVT_count

 

 

 

 

 

 

 

 

25n

Thermo On/Off state_1

nvoThermoSt_n

OUT

 

 

27

SNVT_state

 

 

 

 

 

 

 

 

 

 

26n

Thermo On/Off state_2

nvoThermo_n

OUT

 

 

27

SNVT_switch

 

 

 

 

 

 

 

 

 

 

28n

Model Code

nvoIcMdlSize_n

OUT

(*4)

(*4)

 

 

28

SNVT_count

 

 

 

 

 

 

 

 

 

 

29n

Group Number

nvoGroupNo_n

OUT

(*10)

(*10)

 

(*10)

29

SNVT_count

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

*1: The value "n" is M-NET address of indoor unit

 

 

 

 

 

 

 

 

ex) Request On/Off to the 20th indoor unit.

 

 

 

 

 

 

 

 

nvNo :120

 

 

 

 

 

 

 

 

Name :nviOnOff_020

 

 

 

 

 

 

 

*2: The air conditioner maintenance error (minor fault) is not output.

 

 

 

 

 

 

*3: It may be unable to be used by the system configuration of air-conditioners units or the model of LOSSNAY.

 

 

 

*4: This is not output with LONWORKS network. Monitoring with Poll request or Fetch request is required.

 

 

 

*5: The monitor interval must be set in M-NET with the configuration properties (CP).

 

 

 

 

 

*6: The range (temperature setting, operation mode, wind speed setting) will differ according to the connected devices.

 

 

*7: It is possible to use with an "MA" remote controller (PAR-20MAU) .

 

 

 

 

 

 

*8: When some of the models marketed in July 2002 are used, either MA(PAR-20MAU) or ME(PAR-F27MEA-US) remote controller is required.

 

*9: The interlocked LOSSNAY is run and stopped with operations to each indoor unit.

 

 

 

 

 

*10: It is possible to use with other system controller.

 

 

 

 

 

 