5.Configuration Properties

15Minimum Send Time

network input config SNVT_time_sec nciMinOutTm;

This configuration property defines the minimum send time between the output network variables.

The objective network variables are given below.

Transmitting time is secured per indoor unit. nvoOnOff_nOn/Off run state

nvoMode_nMode state) ・nvoSetP_nSetPoint state

nvoLCMode_nLOSSNAY Mode state) ・nvoFanSpeed_nFanSpeed state

nvoProOnOff_nLocal Prohibit On/Off state) ・nvoProMode_nLocal Prohibit Mode state) ・nvoProSetP_nLocal Prohibit SetPoint state

nvoThermoOff_nForced Thermostat OFF state) ・nvoOnTime_nFilter Run Time

nvoSpaceTemp_nSpace Temperature) ・nvoAlarm_nAlarm state

nvoErrCode_nError Code

nvoErrAdrs_nError Unit Address

nvoThermoSt_nThermo On/Off state_1) ・nvoThermo_nThermo On/Off state_2

Transmitting time is secured per indoor unit. nvoAllOnOffCollective On/Off state

nvoAllOffEmergency state

nvoAllProCollective Local Prohibit state) ・nvoDefrostCollective Defrosting state

nvoAllAlarmCollective Alarm for Indoor Unit

nvoAllAlarmLMAPCollective Alarm for LM ADAPTER

Valid Range

The valid range covers from 1.0 to 600.0 seconds (per 1 second).

The setting to 0.0 or 6553.5 seconds makes the minimum send time setting invalid.

The setting to 0.1 - 0.9 seconds results in 1.0 second.

The setting to 600.1 - 6553.4 seconds results in 600.0 seconds.

Default Value

6553.5 seconds (Setting invalid)