03_NVspec_ver304e
4 Request Collective Operation Prohibit
network input SNVT_switch nviAllPro;
This input network variable is used to collectively prohibit (On/Off, operation mode, temperature setting operations)
of the local remote controller connected to the indoor unit or ventilator (during independent
The effective time is set according to nviEffectTm_2(Effective Time_2).
Valid Range
Collective Operation Prohibit |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
Enable | 1 |
| not used | 1 (*1) |
| 0.5% to 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%.
*This operation is not carried out when there are inputs other than the above. The present instruction state is continued.
Default Value
This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1For the use of this function, turn ON the switch
2It is possible to use with an "MA" remote controller.
5 Collective Local Prohibit state
network output SNVT_switch nvoAllPro;
This output network variable indicates the state of collective operation prohibiting.
Valid Range
Collective Local Prohibit |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
| ||
disable | 0 |
| 0 | 0 |
| 0 |
enable | 1 |
| 0 | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1For the use of this function, turn ON the switch
2It is possible to use with an "MA" remote controller.
- 32 - |