5n Setpoint

network input SNVT_temp_p nviSetPoint_n;

This input network variable is used to change the temperature setpoint of the indoor unit.

Valid Range

HVAC Mode

Range

 

 

Auto mode

19℃ to 28℃

Heat mode

17℃ to 28℃

Cool mode

19℃ to 30℃

Dry mode

19℃ to 30℃

Fan mode

Not available

Unit of set temperature : 1.0℃

*Be careful that the range of set temperature may differ depending on the model of the indoor and outdoor units.

Default Value

The default value is determined by the state of the air conditioner (indoor unit).

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

6n Setpoint state

network output SNVT_temp_p nvoSetPoint_n;

This output network variable indicates the present temperature setpoint of the indoor unit.

Valid Range

Output range: 17 to 30 ℃

Temperature unit: 1.0 ℃

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly as the state changes.

This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller.

This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.

Update Rate

The value defined by nciSndHrtBt_1(SendHearbeat_1) is valid.

Default Service Type

Acknowledged