03_NVspec_ver304e

16Send Heartbeat Start Time

network input config SNVT_time_sec nciStartHrtBt

This configuration property defines the start time of automatic updating at the powering of the LM ADAPTER. The objective configuration properties are given below.

nciSndHrtBt_1Send Heartbeat_1

nciSndHrtBt_2Send Heartrbeat_2

Valid Range

The valid range covers from 1200.0 to 6540.0 seconds (per 60 seconds).

The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.

The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.

The setting to 6540.1- 6553.4 seconds results in 6540.0 seconds.

Default Value

6553.5 seconds (judged as 1800 seconds)

17Send Start Time

network input config SNVT_time_sec nciStartOutTm

This configuration property defines the start time of the output network variable change at powering of LM ADAPTER. The objective network variables are given below.

nvoOnOff_nOn/Off run state) ・nvoMode_nMode state

nvoSetP_nSetPoint state

nvoLCMode_nLOSSNAY Mode state) ・nvoFanSpeed_nFanspeed state

nvoProOnOff_nLocal Prohibit On/Off state) ・nvoProMode_nLocal Prohibit Mode state) ・nvoProSetP_nLocal Prohibit SetPoint state

nvoThermoOff_nForced Thermostat OFF state) ・nvoOnTime_nFilter Run Time

nvoSpaceTemp_nSpace Temperature) ・nvoAlarm_nAlarm state

nvoErrCode_nError Code

nvoErrAdrs_nError Unit Address

nvoThermoSt_nThermo On/Off state_1) ・nvoThermo_nThermo On/Off state_2) ・nvoAllOnOffCollective On/Off state

nvoAllOffEmergency state

nvoAllProCollective local prohibit state) ・nvoDefrostCollective Defrosting state

nvoAllAlarm(Collective Alarm for Indoor Unit)

nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)

Valid Range

The valid range covers from 1200.0 to 6540.0 seconds (per 60 seconds). The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.

The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.

The setting to 6540.1 6553.4 seconds results in 6540.0 seconds.

Output data is as follows by setup of Variable A and Variable B.

Default Value

6553.5 seconds (judged as 1800 seconds)

NOTE: Output data is as follows by setup "Initialize Start Time" and "Communication Timing". Setting "Initialize":

An initial output value or a value at a power supply ON to the time of 20-minute progress. Setting "setting time":

An initial output value or a value at the time of Neuron Chip communication start.

WSN02-2124

- 37 -