03_NVspec_ver304e

1-3.Functions

 

Item

nv

Description

 

No.

 

 

 

 

 

 

 

Operation

Request All Off

nv1

Stops the operation of all air conditioners.

The ON/OFF operation is invalid during emergency stop.

 

 

 

 

Request On/Off

nv1n

Run and stop operation.

 

 

 

 

 

Request Mode

nv3n

Sets the operation mode.

 

 

 

 

 

Setpoint

nv5n

Sets the temperature.

 

 

 

 

 

Request LOSSNAY Mode

nv7n

Sets the LOSSNAY operation mode.

 

 

 

 

 

Request FanSpeed

nv9n

Sets the fan speed.

 

 

 

 

 

Request Local Prohibit On/Off

nv11n

Sets the local remote controller to operation prohibit (On/Off).

 

 

 

 

 

Request Local Prohibit Mode

nv13n

Sets the local remote controller to operation prohibit (operation mode).

 

 

 

 

 

Request Local Prohibit SetPoint

nv15n

Sets the local remote controller to operation prohibit (temperature setting).

 

 

 

 

 

Request Collective Local Prohibit

nv4

Sets the local remote controllers of all air conditioners to operation prohibit

 

(On/Off, operation mode, temperature setting).

 

 

 

 

Request Forced Thermostat OFF

nv17n

Forcibly turns the air conditioner thermostat OFF.

 

 

 

 

 

Filter Sign Reset

nv19n

The run time (for filter) of air conditioner is reset.

 

 

 

 

 

Time Stamp

nv12

Sets the local remote controller time.

 

 

 

 

 

Request Limit Temperature Setting Range

nv13

Sets the temperature setting range of local remote controller.

 

 

 

 

 

Request Simplified Locking

nv14

Sets the local remote controller switch's simple lock, and displays the mode and

 

 

 

intake temperature.

Monitor

Emergency state

nv3

Output the emergency stop state.

 

 

 

 

 

On/Off state

nv2n

Outputs the On/Off state.

 

 

 

 

 

Collective On/Off state

nv2

Outputs the On/Off state for all air conditioners.

 

 

 

 

 

Mode state

nv4n

Outputs the operation mode setting state.

 

 

 

 

 

Setpoint State

nv6n

Outputs the temperature setting state.

 

 

 

 

 

LOSSNAY Mode State

nv8n

Outputs the LOSSNAY operation mode setting state.

 

 

 

 

 

FanSpeed state

nv10n

Outputs the fan speed setting state.

 

 

 

 

 

Local Prohibit On/Off State

n12n

Outputs the local remote controller operation prohibit (On/Off) state.

 

 

 

 

 

Local Prohibit Mode State

nv14n

Outputs the local remote controller operation prohibit (operation mode) state.

 

 

 

 

 

Local Prohibit SetPoint State

nv16n

Outputs the local remote controller operation prohibit (temperature setting)

 

 

 

state.

 

Collective Local Prohibit State

nv5

Outputs the local remote controller collective operation prohibit state.

 

 

 

 

 

Forced Thermostat OFF State

nv18n

Outputs the forced thermostat OFF state.

 

 

 

 

 

Run Time for Filter

nv20n

Outputs the run time (for filter) of air conditioner.

 

 

 

 

 

Space Temperature State

nv21n

Outputs the intake temperature of air conditioner.

 

 

 

 

 

Defrost State

nv9

Outputs the defrosting state of indoor unit or outdoor unit.

 

 

 

 

 

Group Number

nv29n

Outputs the group number of the indoor unit.

 

 

 

 

 

Alarm State

nv22n

Outputs the presence of air conditioner errors.

 

 

 

 

 

Collective Alarm for Indoor Unit

nv6

Outputs the presence of errors in all air conditioners.

 

 

 

 

 

Collective Alarm for LM ADAPTER

nv7

Outputs the presence of communication errors between the LM ADAPTER and

 

air conditioner.

 

 

 

 

Error Code

nv23n

Outputs the presence of air conditioner errors content (error code).

 

 

 

 

 

Error Address

nv24n

Outputs the error source (M-NET address) when an air conditioner error occurs.

 

 

 

 

 

Thermo On/Off state_1 (*1)

nv25n

Outputs the air conditioner operation, thermostat and auxiliary heater states.

 

 

 

 

 

Thermo On/Off state_2 (*1)

nv26n

Outputs the thermostat state.

 

 

 

 

 

Model Code (*1)

nv28n

Outputs the air conditioner model code.

 

 

 

 

 

 

 

 

Note

*1: This product does not have a charge function.

The charge (apportioning) function must be prepared separately in the master system.

WSN02-2124