2-4.Indoor unit

 

 

 

Indoor[1]-[50]

 

 

 

Network Variables

 

nv1n

nviOnOff_n

nv2n

 

SNVT_switch

 

 

 

 

nv3n

nviMode_n

nv4n

 

SNVT_hvac_mode

 

 

 

 

nv5n

nviSetP_n

nv6n

 

SNVT_temp_p

 

 

 

 

nv9n

nviFanSpeed_n

nv10n

 

SNVT_switch

 

 

 

*3,4,5

nv11n

nviProOnOff_n

nv12n

SNVT_switch

 

 

 

*3,4,5

nv13n

nviProMode_n

nv14n

SNVT_switch

 

 

 

*3,4,5

nv15n

nviProSetP_n

nv16n

SNVT_switch

 

 

 

*6

nv17n

nviThermoOff_n

nv18n

SNVT_switch

 

 

 

*7

nv19n

nviFiltReset_n

nv20n

SNVT_switch

nv21n

nv22n

nv23n

nv24n

nv25n

nv26n

nv28n

nc29n

nvoOnOff_n SNVT_ switch

nvoMode_n

SNVT_hvac_mode

nvoSetP_n

SNVT_temp_p

nvoFanSpeed_n SNVT_switch

nvoProOnOff_n SNVT_switch

nvoProMode_n SNVT_switch

nvoProSetP_n SNVT_switch

nvoThermoOff_n SNVT_switch

nvoOnTime_n

SNVT_time_hour

nvoSpaceTemp_n

SNVT_temp_p

nvoAlarm_n SNVT_switch

nvoErrCode_n

SNVT_count

nvoErrAdrs_n SNVT_count

nvoThermoSt_n

SNVT_state

nvoThermo_n SNVT_switch

nvoIcMdlSize_n SNVT_count

nvoGroupNo_n SNVT_count

03_NVspec_ver304e

*3,4,5

*3,4,5

*3,4,5

*6

*7

*8

Notes

*1: stencil for LonMaker:Indoor[1]-[50]

*2: "n" of the network variable shows M-NET address of indoor units.

*3: It may be unable to be used by the system configuration of air-conditioners units.

*4: It is possible to use with an "MA" remote controller.

*5: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF")

*6: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF")

*7: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting "OFF")

*8: It is possible to use with other system controller.

WSN02-2124

- 7 -