03_NVspec_ver304e

4.Network Variables

1n Request On/Off

network input SNVT_switch nviOnOff_n;

This input network variable is used to run or stop the indoor unit or ventilator (during independent non-interlocked operation).

When the ventilator (LOSSNAY) is registered as interlocking with indoor unit, it will turn the indoor unit ON (for high speed) and OFF. Instructions according to this network variable in under nvoAllOff's output of the state of "Emergency Off" are disregarded.

Valid Range

 

Unit State

 

SW1-7OFF

 

SW1-7O

indoor unit

 

interlocked ventilator

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

 

OFF

0

 

0% to 99.5 % (*1)

0

 

not used

OFF

 

 

1 (*2)

 

0

 

 

 

 

 

 

 

 

ON(high)

0

 

100% (*1,3)

 

 

 

ON

 

ON(high)

1

 

not used

1 (*2)

 

0.5% to 100% (*3)

 

else

 

not used

 

 

 

 

 

 

 

 

*1:The value field is set in 0% usually.

*2:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*3:The setting to over 100% is interpreted as 100%.

Default Value

The default value is determined by the state of the air conditioner (indoor unit).

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

2n On/Off run state

network output SNVT_switch nvoOnOff_n;

This output network variable indicates the present On/Off state of the indoor unit or ventilator.

When the ventilator (LOSSNAY) is registered interlocking with the indoor unit, the state of the ventilator will not be output, but it will operate (On/Off) the same as the indoor unit.

Valid Range

 

Unit State

 

SW1-7OFF

 

SW1-7O

indoor unit

 

interlocked ventilator

state

 

value

state

 

value

 

 

 

 

 

 

 

 

OFF

 

OFF

0

 

0%

 

 

 

 

 

ON(low)

0

 

50%

0

 

0

 

 

ON(high)

0

 

100%

 

 

 

ON

 

any

1

 

0

1

 

100%

When Transmitted

This variable is transmitted promptly as its state changes.

This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller.

This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.

Update Rate

The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.

Default Service Type

Acknowledged

WSN02-2124

- 14 -