03_NVspec_ver304e

19Initialize Send Time_1

network input config SNVT_time_sec nciInitOutTm_1

This configuration property defines the minimum send time between the output network variables at initial output. This configuration is valid when setting the Initialize Start Time to other values than 0.0 second.

The objective network variables are given below. nvoOnOff_nOn/Off run state

nvoMode_nMode state) ・nvoSetP_nSetPoint state) ・nvoAlarm_nAlarm state) ・nvoErrCode_nError Code

nvoErrAdrs_nError Unit Address

nvoThermoSt_nThermo On/Off state_1) ・nvoThermo_nThermo On/Off state_2) ・nvoAllOnOffCollective On/Off state

nvoAllOffEmergency state

nvoAllAlarm(Collective Alarm for Indoor Unit)

nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)

Valid Range

The valid range covers from 0.1 to 1.0 second (per 100m seconds).

The setting to 0.0 or 6553.5 seconds makes the initial output minimum send time setting invalid. The setting to 1.1 - 6553.4 seconds results in 1.0 second.

Default Value

6553.5 seconds (Setting invalid)

20Initialize Send Time_2

network input config SNVT_time_sec nciInitOutTm_2

This configuration property defines the minimum send time between each unit of the indoor, Mr.SLIM and ventilator at the initial output.

This configuration is valid when setting the Initialize Start Time to other values than 0.0 second. The objective network variables are given below.

nvoOnOff_nOn/Off run state) ・nvoMode_nMode state

nvoSetP_nSetPoint state) ・nvoAlarm_nAlarm state) ・nvoErrCode_nError Code

nvoErrAdrs_nError Unit Address

nvoThermoSt_nThermo On/Off state_1) ・nvoThermo_nThermo On/Off state_2) ・nvoAllOnOffCollective On/Off state

nvoAllOffEmergency state

nvoAllAlarm(Collective Alarm for Indoor Unit)

nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)

Valid Range

The valid range covers from 5.0 to 50.0 second (per 1second).

The setting to 0.0 or 6553.5 seconds makes the initial output minimum send time setting invalid. The setting to 0.1 - 4.9 seconds results in 5.0 seconds.

The setting to 50.1 - 6553.4 seconds results in 50.0 seconds.

Default Value

6553.5 seconds (Setting invalid)

WSN02-2124