2-6.LOSSNAY

(1)LOSSNAY interlocks with the indoor unit.(*1,3)

Indoor[1]-[50]

Network Variables

nv22n

nv23n

nv24n

(2)LOSSNAY is operated from LONWORKS.(*5,6,7)

 

 

 

Indoor[1]-[50]

 

 

 

Network Variables

 

nv1n

nviOnOff_n

nv2n

 

SNVT_switch

 

 

 

*4

nv7n

nviLCMode_n

nv8n

SNVT_switch

 

 

 

 

nv9n

nviFanSpeed_n

nv10n

 

SNVT_switch

 

 

 

*8,9,10

nv11n

nviProOnOff_n

nv12n

SNVT_switch

 

 

 

*11

nv19n

nviFiltReset_n

nv20n

SNVT_switch

nv22n

nv23n

nv24n

nc29n

nvoAlarm_n SNVT_switch

nvoErrCode_n

SNVT_count

nvoErrAdrs_n SNVT_count

nvoOnOff_n SNVT_ switch

nvoLCMode_n SNVT_switch

nvoFanSpeed_n SNVT_switch

nvoProOnOff_n SNVT_switch

nvoOnTime_n

SNVT_time_hour

nvoAlarm_n SNVT_switch

nvoErrCode_n

SNVT_count

nvoErrAdrs_n SNVT_count

nvoGroupNo_n SNVT_count

03_NVspec_ver304e

*4

(*4)

(*8,9,10)

(*11)

(*4)

*12

Notes:

*1: stencil for LonMaker:iLOSSNAY[1]-[50]

*2: "n" of the network variable shows M-NET address of LOSSNAY.

*3: LOSSNAY is not controlled from a LONWORKS network.

*4: It may be unable to be used by the system configuration of air-conditioners units or the model of LOSSNAY.

*5: LOSSNAY is controlled from a LONWORKS network.

*6: stencil for LonMaker:LOSSNAY[1]-[50]

*7: Please turn ON the switch(SW1-5) when LOSSNAY is operation from LONWORKS.(Factory setting "OFF")

*8: There is a case which cannot be used with the system configuration of the air-conditioners units.

*9: It is possible to use with an "MA" remote controller.

*10: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF")

*11: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF")

*12: It is possible to use with other system controller.

WSN02-2124