3n Request mode
network input SNVT_hvac_mode nviMode_n;
This input network variable is used to change the operation mode of the indoor unit.
Some operation modes may not be compatible depending on the model.
Valid Range
value | definition | Active mode |
|
|
|
0 | HVAC_AUTO | Auto mode |
1 | HVAC_HEAT | Heat mode |
3 | HVAC_COOL | Cool mode |
5 | HVAC_PRE_COOL | Dry mode |
9 | HVAC_FAN_ONLY | Fan mode |
else | - | Fan mode |
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
4n Mode state
network output SNVT_hvac_mode nvoMode_n;
This output network variable indicates the present mode of the indoor unit.
Valid Range
value | definition | Active mode |
|
|
|
0 | HVAC_AUTO | Auto mode |
1 | HVAC_HEAT | Heat mode |
3 | HVAC_COOL | Cool mode |
5 | HVAC_PRE_COOL | Dry mode |
9 | HVAC_FAN_ONLY | Fan mode |
FF | HVAC_NUL | value not available |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) is valid.
Default Service Type
Acknowledged
NOTE:
1:It is necessary to make all the indoor units in the same refrigerant system into the same operation mode depending on a model. "HVAC_NUL" may be outputted when it is set as different operation mode.
2:Depending on the change timing, "HVAC_NUL" may be outputted temporarily.