18Initialize Start Time

network input config SNVT_time_sec nciInitStartTm

This configuration property defines the time to start the output when the output network variables change at LM ADAPTER power ON.

The objective network variables are given below. nvoOnOff_nOn/Off run state

nvoMode_nMode state) ・nvoSetP_nSetPoint state) ・nvoAlarm_nAlarm state) ・nvoErrCode_nError Code

nvoErrAdrs_nError Unit Address

nvoThermoSt_nThermo On/Off state_1) ・nvoThermo_nThermo On/Off state_2) ・nvoAllOnOffCollective On/Off state

nvoAllOffEmergency state

nvoAllAlarm(Collective Alarm for Indoor Unit)

nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)

Valid Range

The valid range covers from 0.0,1200.0 to 3600.0 seconds (per 60 seconds).

The setting to 0.0 or 6553.5 seconds makes the initial output time setting invalid.

The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.

The setting to 3600.1 6553.4 seconds results in 3600.0 seconds.

Default Value

6553.5 seconds (Setting invalid)