03_NVspec_ver304e

1 Request All Off

network input SNVT_switch nviAllOff;

This input network variable is used for the emergency Off of the indoor unit and all ventilation.

Under the output of "Emergency OFF" of nvoAllOff cannot operate from other remote controller ,system controller. The ON/OFF input for each indoor unit from the master system will be ignored. The emergency stop valid time is set with nciEffectTm_1 (Effective time 1).

The indoor unit will not start even if the emergency stop is cancelled.

Valid Range

 

 

SW1-7OFF

 

SW1-7O

 

state

 

value

state

 

value

 

 

 

 

 

 

 

emergency OFF

0

 

not used

0

 

not used

 

1 (*1)

 

0

 

 

 

 

 

*1:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*This operation is not carried out when there are inputs other than the above. The present instruction state is continued.

Default Value

This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.

NOTE: Input the "On" command with nviOnOff (Request ON/OFF) to start the indoor unit after emergency stop is cancelled.

3 Emergency state

network output SNVT_switch nvoAllOff;

This output network variable indicates the emergency stop validity state.

Valid Range

Emergency state

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

normal

0

 

0

0

 

0

Emergency OFF

1

 

0

1

 

100%

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly when the state changes.

This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.

Update Rate

This network variable is outputted every 10 minutes.

Default Service Type

Acknowledged

WSN02-2124

- 30 -