03_NVspec_ver304e
1 Request All Off
network input SNVT_switch nviAllOff;
This input network variable is used for the emergency Off of the indoor unit and all ventilation.
Under the output of "Emergency OFF" of nvoAllOff cannot operate from other remote controller ,system controller. The ON/OFF input for each indoor unit from the master system will be ignored. The emergency stop valid time is set with nciEffectTm_1 (Effective time 1).
The indoor unit will not start even if the emergency stop is cancelled.
Valid Range
|
|
| ||||
| state |
| value | state |
| value |
|
|
|
|
|
|
|
emergency OFF | 0 |
| not used | 0 |
| not used |
| 1 (*1) |
| 0 | |||
|
|
|
|
|
*1:The setting to
*This operation is not carried out when there are inputs other than the above. The present instruction state is continued.
Default Value
This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE: Input the "On" command with nviOnOff (Request ON/OFF) to start the indoor unit after emergency stop is cancelled.
3 Emergency state
network output SNVT_switch nvoAllOff;
This output network variable indicates the emergency stop validity state.
Valid Range
Emergency state |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
| ||
normal | 0 |
| 0 | 0 |
| 0 |
Emergency OFF | 1 |
| 0 | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
This network variable is outputted every 10 minutes.
Default Service Type
Acknowledged
- 30 - |