03_NVspec_ver304e
7n Request LOSSNAY Mode
network input SNVT_switch nviLCMode_n;
This input network variable is used to change the operation mode of the ventilator (at independent operation without interlocking) .
This nv is not required to be use when setting the operation mode only from the local side such as a local remote controller.
Valid Range
LOSSNAY Mode |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
Interchange | 0 |
| 0 | 0 |
| not used |
| 1 (*1) |
| 0 | |||
|
|
|
|
| ||
Automatic | 1 |
| not used | 1 (*1) |
| 0.5% to 50% |
else |
| not used |
| |||
|
|
|
|
| ||
Normal | 0 |
| 0.5% to 100% (*2) | 1 (*1) |
| 50.5% to 100% (*2) |
|
|
|
|
| ||
| *1:The setting to | interpreted as state=0x01. | ||||
| The setting to state=0xFF is invalid. |
|
|
| ||
| *2:The setting to over 100% is interpreted as 100%. |
|
|
Default Value
The default value is determined by the state of the ventilator.
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
8n LOSSNAY Mode state
network output SNVT_switch nvoLCMode_n;
This output network variable indicates the present operation mode of the ventilator.
Valid Range
LOSSNAY Mode |
|
| ||||
| state |
| value | state |
| value |
|
|
|
|
| ||
Interchange | 0 |
| 0 | 0 |
| 0 |
Automatic | 1 |
| 0 | 1 |
| 50% |
Normal | 0 |
| 100% | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
It is also transmitted as the state changes by the operation from the local side such as a local remote controller.
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
- 17 - |