03_NVspec_ver304e

7n Request LOSSNAY Mode

network input SNVT_switch nviLCMode_n;

This input network variable is used to change the operation mode of the ventilator (at independent operation without interlocking) .

This nv is not required to be use when setting the operation mode only from the local side such as a local remote controller.

Valid Range

LOSSNAY Mode

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

Interchange

0

 

0

0

 

not used

 

1 (*1)

 

0

 

 

 

 

 

Automatic

1

 

not used

1 (*1)

 

0.5% to 50%

else

 

not used

 

 

 

 

 

 

Normal

0

 

0.5% to 100% (*2)

1 (*1)

 

50.5% to 100% (*2)

 

 

 

 

 

 

*1:The setting to

state=0x02-0xFE is

interpreted as state=0x01.

 

The setting to state=0xFF is invalid.

 

 

 

 

*2:The setting to over 100% is interpreted as 100%.

 

 

Default Value

The default value is determined by the state of the ventilator.

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

8n LOSSNAY Mode state

network output SNVT_switch nvoLCMode_n;

This output network variable indicates the present operation mode of the ventilator.

Valid Range

LOSSNAY Mode

 

SW1-7OFF

 

SW1-7O

 

state

 

value

state

 

value

 

 

 

 

 

Interchange

0

 

0

0

 

0

Automatic

1

 

0

1

 

50%

Normal

0

 

100%

1

 

100%

The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly as the state changes.

It is also transmitted as the state changes by the operation from the local side such as a local remote controller.

Update Rate

The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.

Default Service Type

Acknowledged

WSN02-2124

- 17 -