03_NVspec_ver304e
19n Filter Sign Reset
network input SNVT_switch nviFiltReset_n;
This input network variable resets the run time and filter sign for the indoor unit or ventilator (during independent
Valid Range
|
|
| ||||
| state |
| value | state |
| value |
|
|
|
|
|
|
|
Reset | 1 |
| not used | 1(*1) |
| 0.5% to 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%. *The value is 0 while LM ADAPTER is initialized.
*This operation is not carried out when there are inputs other than the above.
Default Value
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
20n Filter Run Time
network output SNVT_time_hour nvoOnTime_n;
This output network variable indicates the filter operation time for the indoor unit or ventilator (during independent
Valid Range
0~65,534 hour
*The value is 0 while LM ADAPTER is initialized.
*The valid range will differ according to the indoor unit or ventilator model.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: For the use of this function, turn ON the switch
- 23 - |