03_NVspec_ver304e

19n Filter Sign Reset

network input SNVT_switch nviFiltReset_n;

This input network variable resets the run time and filter sign for the indoor unit or ventilator (during independent non-interlocked operation).

Valid Range

 

 

SW1-7OFF

 

SW1-7O

 

state

 

value

state

 

value

 

 

 

 

 

 

 

Reset

1

 

not used

1(*1)

 

0.5% to 100% (*2)

*1:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*2:The setting to over 100% is interpreted as 100%. *The value is 0 while LM ADAPTER is initialized.

*This operation is not carried out when there are inputs other than the above.

Default Value

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

20n Filter Run Time

network output SNVT_time_hour nvoOnTime_n;

This output network variable indicates the filter operation time for the indoor unit or ventilator (during independent non-interlocked operation).

Valid Range

065,534 hour

*The value is 0 while LM ADAPTER is initialized.

*The valid range will differ according to the indoor unit or ventilator model.

When Transmitted

This variable is transmitted promptly as the state changes.

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE: For the use of this function, turn ON the switch (SW1-4) on LM ADAPTER.(Factory setting "OFF")

WSN02-2124

- 23 -