31Effective Offline Mode
network input config SNVT_switch nciOffline;
This configuration property defines the offline mode setting when the LM adaptor power is turned ON. This setting is valid only for 15 minutes after the LM adaptor power is turned ON.
A Null response is returned if a Poll/Fetch request is issued to the network variables during the offline state. The objective variable is given below.
・nvoOnOff_n(On/Off run state) ・nvoMode_n(Mode state)
・nvoSetP_n(SetPoint state)
・nvoLCMode_n(LOSSNAY Mode state) ・nvoFanSpeed_n(Fanspeed state)
・nvoProOnOff_n(Local Prohibit On/Off state) ・nvoProMode_n(Local Prohibit Mode state) ・nvoProSetP_n(Local Prohibit SetPoint state)
・nvoThermoOff_n(Forced Thermostat OFF state) ・nvoOnTime_n(Filter Run Time)
・nvoSpaceTemp_n(Space Temperature) ・nvoAlarm_n(Alarm state)
・nvoErrCode_n(Error Code)
・nvoErrAdrs_n(Error Unit Address)
・nvoThermoSt_n(Thermo On/Off state_1) ・nvoThermo_n(Thermo On/Off state_2) ・nvoAllOnOff(Collective On/Off state)
・nvoIcMdlsize_n(Model Code)
・nvoAllAlarm(Collective Alarm for Indoor Unit) ・nvoAllOff_n(Emergency state)
・nvoAllPro(Request Collective Local Prohibit)
・nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)
Valid Range
Offline Mode |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
disable | 0 |
| not used | 0 |
| not used |
else |
| not used | 1 (*1) |
| 0 | |
|
|
| ||||
enable | 1 |
| not used | 1 (*1) |
| 0.5% - 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%.
Default Value
0(Setting invalid) *Always