03_NVspec_ver304e
1.Specification1-1.Object Model
These specifications apply to the communication interface used to connect the LonWorks network and the Mitsubishi Electric
<Model name>
1.Multiple split type air conditioners CITY MULTI
2.
3. Heat recovery ventilators LOSSNAY
NOTE:LOSSNAY
1-2.Explanation of Function Setting
This product requires a function setting switch because of the connected model, system configuration and control functions.
SW NO. | switch name |
| Function | Note | Factory | Set timing | |
| setting | ||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
SW1-1 | Function switch of local prohibit | ON | local prohibit effective | Operation local prohibit NV input from | OFF | Before turning on | |
LONWORKS becomes Effective when switch ON. | the power supply | ||||||
|
|
|
|
| |||
|
| OFF | local prohibit ineffective | Operation local prohibit NV input from |
|
| |
|
| LONWORKS becomes invalid when switch OFF |
|
| |||
|
|
|
|
|
| ||
SW1-2 | Used together with MELANS | ON | used together with MELANS *4 |
| OFF | Before turning on | |
switch |
| the power supply | |||||
|
|
|
|
| |||
| *2 | OFF | not used together with MELANS |
|
|
| |
|
|
| *5 |
|
|
| |
SW1-3 | Indoor temperature state | ON | Transmission interval | *The number of indoor units connected should b | OFF | Before turning on | |
| interval switch |
| (1minutes or more) | 30 or less *6 |
| the power supply | |
|
| OFF | Transmission interval |
|
|
| |
|
|
| (10 minutes or more) |
|
|
| |
SW1-4 | Reset Filtersign/Select | ON | effective | When "ON",the reset filter sign input and the | OFF | Before turning on | |
enable/disable operation duration | operation duration output are enabled. | the power supply | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
| OFF | ineffective | When "OFF",the reset filter sign input and the |
|
| |
|
| operation duration output are disabled |
|
| |||
|
|
|
|
|
| ||
SW1-5 | Function switch of LOSSNAY | ON | LOSSNAY is operated | Please turn on the switch when LOSSNAY | OFF | Before turning on | |
from LONWORKS. | is operated from LONWORKS. | the power supply | |||||
| *3 | OFF | LOSSNAY interlocks | Please turn off the switch when LOSSNAY |
|
| |
|
|
| with indoor units | interlocks with indoor units |
|
| |
SW1-7 | Function switch of SNVT_switch | ON | SNVT standard | When "ON",the specifications of the NV using the | OFF | Before turning on | |
SNVT_switch comply with the SNVT Standards. | the power supply | ||||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
| OFF | original | When "OFF",the NV using the SNVT_switch has |
|
| |
|
| original specifications. |
|
| |||
|
|
|
|
|
| ||
SW1-8 | Select enable/disable forced | ON | effective | When "ON",the forced thermo OFF NV input/outpu | OFF | Before turning on | |
thermostat OFF | are enabled. | the power supply | |||||
|
|
|
| ||||
|
| OFF | ineffective | When "OFF",the forced thermo OFF NV |
|
| |
|
| input/output are disabled |
|
| |||
|
|
|
|
|
| ||
SW1-9 | Indoor units test run switch | ON | ON (test run) is transmitted |
| OFF | Always | |
to the indoor units |
| ||||||
|
| OFF | OFF is transmitted |
|
|
| |
|
|
| to the indoor units |
|
|
| |
| Initialization switch of | ON | Connected cancellation |
| OFF | Always | |
SW3-2 | command is transmitted to |
| |||||
the air conditioners units |
| ||||||
|
| the indoor units |
|
|
| ||
|
|
|
|
|
| ||
|
| OFF | None |
|
|
|
Notes:
*1: Always use together with the local remote controller or system controller.
*2: Always register the LM ADAPTER as a system controller when using together with the system controller.
*3: The functions used with the LM ADAPTER are changed. The air conditioner and LOSSNAY cannot be set to interlock with the LM ADAPTER. Set with the system controller or local remote controller.
*4: Carry out an instruction input at the unit of the lowest address unit in the same group. The instructions to other units are disregarded. However, a state output is output for every unit. Forced thermostat OFF needs an instruction input for every unit.
*5: Input the same instructions to all the units in the same group.
*6: Make a monitor interval into 1 minute, and when you use both the functions of "local prohibit", and the "forced thermostat OFF", give 25 sets or less.
- 2 - |