03_NVspec_ver304e

1.Specification

1-1.Object Model

These specifications apply to the communication interface used to connect the LonWorks network and the Mitsubishi Electric M-NET compatible products.

<Model name>

1.Multiple split type air conditioners CITY MULTI

2.Split-type air conditioners Mr.SLIM

NOTE:A-M Converter(PAC-SF48MA-E) is necessary.

3. Heat recovery ventilators LOSSNAY

NOTE:LOSSNAY Adapter(PZ-53ADF-E) is necessary.

1-2.Explanation of Function Setting

This product requires a function setting switch because of the connected model, system configuration and control functions.

SW NO.

switch name

 

Function

Note

Factory

Set timing

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1-1

Function switch of local prohibit

ON

local prohibit effective

Operation local prohibit NV input from

OFF

Before turning on

LONWORKS becomes Effective when switch ON.

the power supply

 

 

 

 

 

 

 

OFF

local prohibit ineffective

Operation local prohibit NV input from

 

 

 

 

LONWORKS becomes invalid when switch OFF

 

 

 

 

 

 

 

 

SW1-2

Used together with MELANS

ON

used together with MELANS *4

 

OFF

Before turning on

switch

 

the power supply

 

 

 

 

 

 

*2

OFF

not used together with MELANS

 

 

 

 

 

 

*5

 

 

 

SW1-3

Indoor temperature state

ON

Transmission interval

*The number of indoor units connected should b

OFF

Before turning on

 

interval switch

 

(1minutes or more)

30 or less *6

 

the power supply

 

 

OFF

Transmission interval

 

 

 

 

 

 

(10 minutes or more)

 

 

 

SW1-4

Reset Filtersign/Select

ON

effective

When "ON",the reset filter sign input and the

OFF

Before turning on

enable/disable operation duration

operation duration output are enabled.

the power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

ineffective

When "OFF",the reset filter sign input and the

 

 

 

 

operation duration output are disabled

 

 

 

 

 

 

 

 

SW1-5

Function switch of LOSSNAY

ON

LOSSNAY is operated

Please turn on the switch when LOSSNAY

OFF

Before turning on

from LONWORKS.

is operated from LONWORKS.

the power supply

 

*3

OFF

LOSSNAY interlocks

Please turn off the switch when LOSSNAY

 

 

 

 

 

with indoor units

interlocks with indoor units

 

 

SW1-7

Function switch of SNVT_switch

ON

SNVT standard

When "ON",the specifications of the NV using the

OFF

Before turning on

SNVT_switch comply with the SNVT Standards.

the power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

original

When "OFF",the NV using the SNVT_switch has

 

 

 

 

original specifications.

 

 

 

 

 

 

 

 

SW1-8

Select enable/disable forced

ON

effective

When "ON",the forced thermo OFF NV input/outpu

OFF

Before turning on

thermostat OFF

are enabled.

the power supply

 

 

 

 

 

 

OFF

ineffective

When "OFF",the forced thermo OFF NV

 

 

 

 

input/output are disabled

 

 

 

 

 

 

 

 

SW1-9

Indoor units test run switch

ON

ON (test run) is transmitted

 

OFF

Always

to the indoor units

 

 

 

OFF

OFF is transmitted

 

 

 

 

 

 

to the indoor units

 

 

 

 

Initialization switch of

ON

Connected cancellation

 

OFF

Always

SW3-2

command is transmitted to

 

the air conditioners units

 

 

 

the indoor units

 

 

 

 

 

 

 

 

 

 

 

OFF

None

 

 

 

Notes:

*1: Always use together with the local remote controller or system controller.

*2: Always register the LM ADAPTER as a system controller when using together with the system controller.

*3: The functions used with the LM ADAPTER are changed. The air conditioner and LOSSNAY cannot be set to interlock with the LM ADAPTER. Set with the system controller or local remote controller.

*4: Carry out an instruction input at the unit of the lowest address unit in the same group. The instructions to other units are disregarded. However, a state output is output for every unit. Forced thermostat OFF needs an instruction input for every unit.

*5: Input the same instructions to all the units in the same group.

*6: Make a monitor interval into 1 minute, and when you use both the functions of "local prohibit", and the "forced thermostat OFF", give 25 sets or less.