11Request Local Prohibit On/Off

network input SNVT_switch nviProOnOff_n;

This input network variable is used to prohibit the On/Off operation of the local remote controller connected to the indoor unit or ventilator (under independent operation without interlocking).

When the ventilator is registered to be interlocked with the indoor unit, the On/Off operation of the ventilator will also be prohibited.

Instructions according to this network variable in under the prohibition of collective operation (nvoAllPro outputs "Enable") are held.

The operation prohibit setting will be cancelled when the time set with nciRcvHrtBt_1 (Receive Heartbeat 1) elapses , so periodic updating is required.

Valid Range

Prohibit/Permit

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

Permit

0

 

not used

0

 

not used

else

 

not used

1 (*1)

 

0

 

 

 

Prohibit

1

 

not used

1 (*1)

 

0.5% to 100% (*2)

 

*1:The setting to

state=0x02-0xFE is

interpreted as state=0x01.

 

The setting to state=0xFF is invalid.

 

 

 

 

*2:The setting to over 100% is interpreted as 100%.

 

 

Default Value

The default value permit On/Off operation of local remote controller

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

NOTE:

1For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")

2It is possible to use with an "MA" remote controller.

12Local Prohibit On/Off state

network output SNVT_switch nvoProOnOff_n;

This output network variable indicates the prohibit/permit state for the On/Off of the local remote controller connected to the indoor unit or ventilator.

Valid Range

Prohibit/Permit

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

Permit

0

 

0

0

 

0

Prohibit

1

 

0

1

 

100%

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly as the state changes.

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE:

1For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")

2It is possible to use with an "MA" remote controller.