03_NVspec_ver304e
11n Request Local Prohibit On/Off
network input SNVT_switch nviProOnOff_n;
This input network variable is used to prohibit the On/Off operation of the local remote controller connected to the indoor unit or ventilator (under independent operation without interlocking).
When the ventilator is registered to be interlocked with the indoor unit, the On/Off operation of the ventilator will also be prohibited.
Instructions according to this network variable in under the prohibition of collective operation (nvoAllPro outputs "Enable") are held.
The operation prohibit setting will be cancelled when the time set with nciRcvHrtBt_1 (Receive Heartbeat 1) elapses , so periodic updating is required.
Valid Range
Prohibit/Permit |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
Permit | 0 |
| not used | 0 |
| not used |
else |
| not used | 1 (*1) |
| 0 | |
|
|
| ||||
Prohibit | 1 |
| not used | 1 (*1) |
| 0.5% to 100% (*2) |
| *1:The setting to | interpreted as state=0x01. | ||||
| The setting to state=0xFF is invalid. |
|
|
| ||
| *2:The setting to over 100% is interpreted as 100%. |
|
|
Default Value
The default value permit On/Off operation of local remote controller
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1For the use of this function, turn ON the switch
2It is possible to use with an "MA" remote controller.
12n Local Prohibit On/Off state
network output SNVT_switch nvoProOnOff_n;
This output network variable indicates the prohibit/permit state for the On/Off of the local remote controller connected to the indoor unit or ventilator.
Valid Range
Prohibit/Permit |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
| ||
Permit | 0 |
| 0 | 0 |
| 0 |
Prohibit | 1 |
| 0 | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1For the use of this function, turn ON the switch
2It is possible to use with an "MA" remote controller.
- 19 - |