34Lower Setpoint Cooling
network input config SNVT_temp_p nciCoolLrSetP;
This configuration property defines the temperature setting value for local remote controller cool/dry operation. The value is set according to nviRmLim (local remote controller temperature range setting).
Valid Range
The valid range covers from 19.0 to 30.0 second (per 1.0 ℃).
The setting to
The setting to 30.01 - 327.66 ℃ results in 30.0℃.
Default Value
NOTE: It is possible to use with an "ME" remote controller.
35Upper Setpoint Heating
network input config SNVT_temp_p nciHeatUpSetP;
This configuration property defines the upper limit temperature setting value for local remote controller heat operation. The value is set according to nviRmLim (Request Limit Temperature Setting Range).
Valid Range
The valid range covers from 17.0 to 28.0 second (per 1.0 ℃).
The setting to
The setting to 28.01 - 327.66 ℃ results in 28.0℃.
Default Value
NOTE: It is possible to use with an "ME" remote controller.
36Local Operation Lock
network input config SNVT_switch nciRmOpLck;
This configuration property defines the local remote controller simple lock setting value.
The value is set according to nviRmLck (Request Simplified Locking).
Valid Range
Operation Lock |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
All button | 0 |
| not used | 0 |
| not used |
else |
| not used | 1 (*1) |
| 0 | |
|
|
| ||||
except ON/OFF button | 1 |
| not used | 1 (*1) |
| 0.5% - 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%.
Default Value
0(All switches)
NOTE: It is possible to use with an "ME" remote controller.
- 46 - |