03_NVspec_ver304e

34Lower Setpoint Cooling

network input config SNVT_temp_p nciCoolLrSetP;

This configuration property defines the temperature setting value for local remote controller cool/dry operation. The value is set according to nviRmLim (local remote controller temperature range setting).

Valid Range

The valid range covers from 19.0 to 30.0 second (per 1.0 ).

The setting to -273.17 - 18.99 results in 19.0.

The setting to 30.01 - 327.66 results in 30.0.

Default Value

-0.01(judged as 19 )

NOTE: It is possible to use with an "ME" remote controller.

35Upper Setpoint Heating

network input config SNVT_temp_p nciHeatUpSetP;

This configuration property defines the upper limit temperature setting value for local remote controller heat operation. The value is set according to nviRmLim (Request Limit Temperature Setting Range).

Valid Range

The valid range covers from 17.0 to 28.0 second (per 1.0 ).

The setting to -273.17 - 16.99 results in 17.0.

The setting to 28.01 - 327.66 results in 28.0.

Default Value

-0.01(judged as 28 )

NOTE: It is possible to use with an "ME" remote controller.

36Local Operation Lock

network input config SNVT_switch nciRmOpLck;

This configuration property defines the local remote controller simple lock setting value.

The value is set according to nviRmLck (Request Simplified Locking).

Valid Range

Operation Lock

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

All button

0

 

not used

0

 

not used

else

 

not used

1 (*1)

 

0

 

 

 

except ON/OFF button

1

 

not used

1 (*1)

 

0.5% - 100% (*2)

*1:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*2:The setting to over 100% is interpreted as 100%.

Default Value

0(All switches)

NOTE: It is possible to use with an "ME" remote controller.