03_NVspec_ver304e

17n Request Forced Thermostat OFF

network input SNVT_switch nviThermoOff_n;

This input network variable is used to forcibly change indoor unit to the thermo OFF state (Fan mode).

The forced thermo OFF setting will be cancelled when the time set with nciRcvHrtBt_2 (Receive Heartbeat 2) elapses, so periodic updating is required.

Valid Range

Thermostat OFF

 

SW1-7OFF

 

 

SW1-7O

state

 

value*1

 

state

 

value

 

 

 

 

 

 

 

 

 

 

 

disable

0

 

1% to 100% (*3)

 

0

 

not used

else

 

1% to 100% (*3)

 

1 (*2)

 

0

 

 

 

 

 

0

 

0% to 0.5%

 

 

 

 

enable

else

 

0% to 0.5%

 

1 (*2)

 

0.5% to 100% (*3)

 

1

 

not used

 

 

 

 

 

*1:The value field is set in 100% usually.

 

 

 

 

 

*2:The setting to state=0x02-0xFE is interpreted as state=0x01.

 

The setting to state=0xFF is invalid.

 

 

 

 

*3:The setting to over 100% is interpreted as 100%.

 

 

Default Value

The default value is determined by the state of the air conditioner indoor unit).

This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.

18n Forced Thermostat OFF state

network output SNVT_switch nvoThermoOff_n;

This output network variable indicates the current forced thermo OFF state of the indoor unit.

Valid Range

Thermostat OFF

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

disable

0

 

0

0

 

0

enable

1

 

0

1

 

100%

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly as the state changes.

It is also transmitted as the state changes by the operation from the local side such as a local remote controller.

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

WSN02-2124

- 22 -