03_NVspec_ver304e
30Effective PollFetch
network input config SNVT_switch nciPollFetch;
This configuration property defines the presence of a response to the output network variable poll (Fetch) request when an indoor unit is not connected or when communication with the indoor unit is disabled.
The objective variable is given below. ・nvoOnOff_n(On/Off run state)
・nvoMode_n(Mode state) ・nvoSetP_n(SetPoint state)
・nvoLCMode_n(LOSSNAY Mode state) ・nvoFanSpeed_n(Fanspeed state)
・nvoProOnOff_n(Local Prohibit On/Off state) ・nvoProMode_n(Local Prohibit Mode state) ・nvoProSetP_n(Local Prohibit SetPoint state)
・nvoThermoOff_n(Forced Thermostat OFF state) ・nvoOnTime_n(Filter Run Time)
・nvoSpaceTemp_n(Space Temperature) ・nvoAlarm_n(Alarm state)
・nvoErrCode_n(Error Code)
・nvoErrAdrs_n(Error Unit Address)
・nvoThermoSt_n(Thermo On/Off state_1) ・nvoThermo_n(Thermo On/Off state_2) ・nvoAllOnOff(Collective On/Off state)
・nvoIcMdlsize_n(Model Code)
・nvoAllAlarm(Collective Alarm for Indoor Unit)
Valid Range
Poll/Fetch Response |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
response | 0 |
| not used | 0 |
| not used |
else |
| not used | 1 (*1) |
| 0 | |
|
|
| ||||
no response | 1 |
| not used | 1 (*1) |
| 0.5% - 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%.
Default Value
0(Setting invalid) *Always
- 44 - |