03_NVspec_ver304e

6 Collective Alarm for Indoor Unit

network output SNVT_switch nvoAllAlarm;

This output network variable collectively outputs the presence of indoor unit errors(nvoAlarm_n).

Abnormalities will be output if the number of the indoor units in unusual is included.

Valid Range

 

 

SW1-7OFF

 

SW1-7O

 

state

 

value

state

 

value

 

 

 

 

 

normal

0

 

0

0

 

0

Error

1

 

0

1

 

100%

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly when the state changes.

This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

7 Collective Alarm for LM ADAPTER

network output SNVT_switch nvoAllAlarmLMAP;

This output network variable collectively outputs the presence of communication errors between the LM ADAPTER and indoor unit.

If the number of the indoor units in communication is unusual, the abnormalities in communication will be output.

Valid Range

LM ADAPTER state

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

Normal

0

 

0

0

 

0

communication Error

1

 

0

1

 

100%

*The value is 0 while LM ADAPTER is initialized.

When Transmitted

This variable is transmitted promptly when the state changes.

This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE: The communication error are caused with the power supply OFF of an outdoor unit etc.

With the power supply OFF of an indoor unit, communication does not become unusual.

WSN02-2124