03_NVspec_ver304e
9 Collective Defrosting State
network output SNVT_switch nvoDefrost;
This network variable indicated the defrosting state (collective) of indoor unit and outdoor unit.
Valid Range
unit state |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
| ||
Normal | 0 |
| 0 | 0 |
| 0 |
defrosting | 1 |
| 0 | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
12 Time Stamp
network input SNVT_time_stamp nviRmTime;
This input network variable sets the local remote controller's time.
The time is collectively set for all remote controllers (for which the time can be set) connected to
Valid Range
year | not used(0:constantly) |
month | not used(0:constantly) |
day | not used(0:constantly) |
hour | 0 to 23 |
minute | 0 to 59 |
second | 0 to 59 |
Default Value
The value is 0 while LM ADAPTER is initialized.
NOTE: The time is reset when the local remote controller's power is turned OFF, so the time must be set periodically.
- 34 - |