9n Request Fan Speed
network input SNVT_switch nviFanSpeed_n;
This input network variable is used to change the fan speed of the indoor unit or Ventilator (in case of independent operation).
Valid Range
Fan Speed |
|
| ||||
state | value |
| state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
Low | not used | 0% to 25% |
| 0 |
| not used |
| 1 (*1) |
| 0 | |||
|
|
|
|
| ||
not used | 25.5% to 50% | 1 (*1) |
| 0.5% to 50% | ||
not used | 50.5% to 75% | 1 (*1) |
| 50.5% to 75% | ||
High | not used | 75.5% to 100% | (*2) | 1 (*1) |
| 75.5% to 100% (*2) |
*1:The setting to
*2:The setting to over 100% is interpreted as 100%.
*As the number of steps in fan speed differs depending on the model of the indoor unit. Each indoor unit runs as follows. The data received is retained continually.
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
10n Fan Speed state
network output SNVT_switch nvoFanSpeed_n;
This output network variable indicates the present airflow rate of the indoor unit fan.
Valid Range
Fan Speed |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
| ||
Low | 0 |
| 25% | 0 |
| 0 |
0 |
| 50% | 1 |
| 50% | |
0 |
| 75% | 1 |
| 75% | |
High | 0 |
| 100% | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
It is also transmitted as the state changes by the operation from the local side such as a local remote controller.
Update Rate
The value defined by nciSndHrtBt_1(SendHearbeat_1) is valid.
Default Service Type
Acknowledged
- 18 - |