22n Alarm state
network output SNVT_switch nvoAlarm_n;
This output network variable indicates the abnormality of the indoor unit.
If an error occurs in an outdoor unit, the indoor unit will also stop with an error. Thus, the error will be output from all indoor units in the same refrigerant system. (However indoor units under stopping are excluded.)
Valid Range
Unit state |
|
| ||||
state |
| value | state |
| value | |
|
|
| ||||
|
|
|
|
|
|
|
normal | 0 |
| 0 | 0 |
| 0 |
alarm | 1 |
| 0 | 1 |
| 100% |
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1:The release of the indoor unit nvoAlarm_n(Alarm State) results in the "Off" command of the nviOnOff_n (Request On/Off). For the nvoAlarm_n (Alarm State) when the indoor unit is under stopping, transmit "Off",after transmitting "On".
2:The error is not output when the indoor unit is stopped, so always use together with the local remote controller or system controller.
23n Error Code
network output SNVT_count nvoErrCode_n;
This output network variable indicates the indoor unit's error code.
If an error occurs in an outdoor unit, the indoor unit will also stop with an error. Thus, the error will be output from all indoor units in the same refrigerant system. (However indoor units under stopping are excluded.)
Valid Range
0~7999 = Error Code
65,535 = Normal
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1:The release of the indoor unit nvoErrCode_n(Error Code) results in the "Off" command of the nviOnOff_n(Request On/Off) For the nvoErrCode_n(Error Code) when the indoor unit is under stopping, transmit "Off" ,after transmitting "On".
2:The error is not output when the indoor unit is stopped, so always use together with the local remote controller or system controller.