03_NVspec_ver304e

37Local Display_1

network input config SNVT_switch nciRmDsp_1;

This configuration property defines the presence of the automatic actual operation mode display on the local remote controller.

The value is set according to nviRmLck (Request Simplified Locking) and nviRmLim (Request Limit Temperature Setting Range).

Valid Range

Display

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

display

0

 

not used

0

 

not used

else

 

not used

1 (*1)

 

0

 

 

 

no display

1

 

not used

1 (*1)

 

0.5% - 100% (*2)

*1:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*2:The setting to over 100% is interpreted as 100%.

Default Value

0(display)

NOTE: It is possible to use with an "ME" remote controller.

38Local Display_2

network input config SNVT_switch nciRmDsp_2;

This configuration property defines the presence of the automatic actual operation mode display on the local remote controller.

The value is set according to nviRmLck (Request Simplified Locking) and nviRmLim (Request Limit Temperature Setting Range).

Valid Range

display

 

SW1-7OFF

 

SW1-7O

state

 

value

state

 

value

 

 

 

 

 

 

 

 

 

 

display

0

 

not used

0

 

not used

else

 

not used

1 (*1)

 

0

 

 

 

no display

1

 

not used

1 (*1)

 

0.5% - 100% (*2)

*1:The setting to state=0x02-0xFE is interpreted as state=0x01. The setting to state=0xFF is invalid.

*2:The setting to over 100% is interpreted as 100%.

Default Value

0(display)

NOTE: It is possible to use with an "ME" remote controller.

WSN02-2124

- 47 -