GT10/GT30

7.1 Switching Screens

 

 

Function switching parts: Attribute editing dialog box

Double–clicking on the parts arranged on the base screen, or selecting a switch part, and clicking on the “Parts (T)” menu and then the “Edit Attribute” sub–menu displays the dialog box shown above.

(1) Using the “Change Screen” operation mode

Select the “Change Screen” operation mode and specify the number of the screen to be changed. Then press the switch part to switch the screen to the specified screen. To return to the screen displayed just prior to the currently displayed screen, the “Return to Previous Screen” operation mode can be used.

In this case, the value of the third word in the basic communication area / word

device (the number of the currently displayed screen) changes to that of the new screen number, but please be aware that the contents of the first word (the screen number specified by the PLC) do not change. For detailed information, see page 120.

(2) Using the “Value Set” operation mode

Select the “Value Set” operation mode and enter the following settings:

Data format: Specify 1 word

Output destination: Specify to first word of basic communication area / word device

Value: Number of screen to be changed to (hexadecimal specification)

Each time the GT main unit switch part is pressed, the screen number is forcibly written by the GT main unit to the first word of the basic communication area / word device, and the screen is switched.

If using this method, the values for both the first word of the basic communication

area / word device (the screen number specified by the PLC) and the third word (the number of the currently displayed screen) are changed.

Using the auto–paging function

The GT main unit has an “Auto–paging” function that automatically switches the screen to a specified screen number when a certain period of time has elapsed. This function can be used to switch screens automatically.

118