GT10/GT30

4.1 Connecting the FP–Sigma

 

 

4.1Connecting the FP–Sigma

4.1.1Connecting to the COM. Port

FPG–COM1

AFPG801

RS232C

SD RD RS CS SG

FPΣ COM. port

Loose–wire connection

GT10

GT30

MODE

 

TOOL (RS232C) 1 2 3 4ON

24V

OFF

COM. (RS232C)

 

SD RD RS CS GND

 

FPΣ communication format settings

When using COM. Port 1

 

 

When using COM. Port 2

 

 

 

 

 

 

 

 

System

Item

Value Set

System

Item

Value Set

register no.

 

 

 

register no.

 

 

410

COM. Port 1

1

 

411

COM. Port 2

1

 

Unit number

 

 

 

Unit number

 

412

COM. Port 1

Computer link

 

412

COM. Port 2

Computer link

 

Communication

No modem

 

 

Communication

No modem

 

mode

connection

 

 

mode

connection

413

Data length

8 bits

 

414

Data length

8 bits

 

Parity check

Yes, Odd

 

 

Parity check

Yes, Odd

 

Stop bits

1 bit

 

 

Stop bits

1 bit

 

Line return code

CR

 

 

Line return code

CR

 

Start code

No STX

 

 

Start code

No STX

415

COM. Port 1

19200 bits/s

 

415

COM. Port 2

19200 bits/s

 

Communication

 

 

 

Communication

 

 

speed setting

 

 

 

speed setting

 

 

 

 

 

 

 

 

Connecting to the FPΣ COM. port

FPΣ

GT10/GT30

When using the RS232C 1–channel type, the section between the RS and CS signals on the PLC side should be shorted.

When using the RS232C 1–channel type

 

PLC side

 

GT main unit side

Pin no.

Abbreviation

Pin no.

Abbreviation

SD

SD

SD

SD

RD

RD

RD

RD

RS

RS

RS

RS

CS

CS

CS

CS

GND

GND

GND

GND

When using the RS232C 2–channel type

 

PLC side

 

GT main unit side

Pin no.

Abbreviation

Pin no.

Abbreviation

S1

SD

SD

SD

R1

RD

RD

RD

S2

RS

RS

RS

R2

CS

CS

CS

GND

GND

GND

GND