GT10/GT30 | 9.2 What to Do If Something Unusual Occurs (GT30) |
|
|
9.2What to Do If Something Unusual Occurs (GT30)
Problem | Cause | Solution | Related | |
|
|
|
| |
Screen is | 1) Power is not on. | 1) Supply 24V DC power to unit. | ||
blank | 2) (When only lamp and message parts | 2) Check the address of the substitute | GTWIN HELP | |
| ||||
| are configured to the base screen) | reference device and the device val- |
| |
| Value of substitute reference device | ues on the PLC side. |
| |
| value does not exist in substitute data. |
|
| |
|
|
|
| |
Error code | An error has occurred in communication | [Troubleshooting error codes] are listed | ||
[ER**] | between the GT30 and an external de- | on page 142. Refer to this section for de- |
| |
appears at | vice (e.g. PLC). | tails. |
| |
the top right |
|
|
| |
of the screen |
|
|
| |
|
|
|
| |
Screen | There is no base screen data in the | Transfer base screen data from GTWIN. | GTWIN HELP | |
displays | GT30. (Appears even when GT30 con- |
|
| |
[No Screen | figuration data exists.) |
|
| |
data] |
|
|
| |
|
|
|
| |
Screen | 1) Screen settings from the PLC, the | 1) Create and register screen content or | ||
displays | GT30’s switch part or the | specify the correct screen number. |
| |
[Screen No. | indicate an unregistered screen num- | 2) Create and register keyboard screen | GTWIN HELP | |
Error] | ber. | |||
or specify the correct keyboard num- |
| |||
|
|
| ||
| 2) When bringing up the keyboard screen | ber. |
| |
| during data input, an unregistered key- | 3) Transfer base screen data from | GTWIN HELP | |
| board screen number was specified. | |||
| GTWIN. |
| ||
| 3) GT30 configuration data and keyboard |
| ||
|
|
| ||
| screen data exist in the GT30, but |
|
| |
| there is no base screen data. |
|
| |
|
|
|
| |
Screen | The total capacity of transferred base | Delete part of the base screen data so | GTWIN HELP | |
displays | screen data exceeds capacity of the | that the total capacity doesn’t exceed the |
| |
[Memory is | GT30. | capacity of GT30. Data capacity can be |
| |
Full] | (Monochrome: 1.5 M bytes, color: 3.25 M | checked by going to [View (V)] → |
| |
| bytes) | [Memory Usage Conditions] on GTWIN |
| |
|
| menu bar. |
| |
|
|
|
| |
An | 1) The screen specification in the PLC | 1) Specify the correct screen number. | ||
unspecified | screen setting, the GT30 switch part | 2) Check the | page 115 | |
screen | or the | |||
the GT30 configuration settings in |
| |||
appeared / |
|
| ||
2) The startup screen is specified in the | GTWIN. Delete unnecessary settings |
| ||
there is |
| |||
GT30 configuration settings (GTWIN). | and |
| ||
trouble when |
| |||
3) An erroneous device or value is speci- | 3) Check the device content specified on | page 37 to | ||
switching | ||||
screens | fied in the first word of the basic com- | the PLC side in the first word of the | ||
| munication area word device. | basic communication area. (Do not |
| |
|
| use the basic communication area |
| |
|
| with ladder programs.) |
| |
|
|
|
| |
Screen | 1) No screen number has been written to | 1) Specify correct screen number. | ||
doesn’t | the screen setting area (the first word | 2) Refer to page 119 [If the screen does | ||
switch | in the basic communication area word | |||
not change as expected]. (Do not use |
| |||
| device) from the PLC. |
| ||
| the basic communication area with lad- |
| ||
|
|
| ||
| 2) The screen number to which you are | der programs.) |
| |
| attempting to switch has already been |
|
| |
| written from the PLC to the screen set- |
|
| |
| ting area (the first word in the basic |
|
| |
| communication area word device). |
|
| |
|
|
|
|
139