Problem

Cause

 

Solution

Related

 

 

 

 

 

Cannot

1) The screen transfer cable is not con-

 

1) Confirm that the screen transfer cable

GTWIN HELP

transfer data

nected.

 

is correctly and firmly connected.

 

from GTWIN

2) The PC and GT30 COM. port are con-

 

2) Connect to TOOL port with screen

 

 

 

 

 

nected.

 

transfer cable.

 

 

 

 

 

 

* Screen is

An error has occurred in the GT30 sys-

 

1) After confirming the safety of the de-

page 130

blank (power

tem.

 

vice, etc., turn off the power supply

 

supply and

 

 

and then turn it on again. The GT30

 

substitution

 

 

CPU will be reset.

 

settings

 

 

 

 

above are

 

 

 

 

correct)

 

 

2) If 1) produces no change, bring up the

 

* An

 

 

system menu and initialize the

 

incorrect

 

 

memory (F–ROM), then transfer data

 

screen is

 

 

again from GTWIN to the GT30.

 

displayed

 

 

CAUTION:

 

(error codes

 

 

When doing this, all base screen data,

 

and

 

 

GT30 setting data, keyboard screen

 

erroneous

 

 

data, and bitmap data will be lost. Be-

 

date and

 

 

fore doing this, make sure all data has

 

time items

 

 

been backed upage

 

noted above

 

 

 

 

do not

 

 

 

 

apply)

 

 

3) If 2) produces no change, set the op-

 

* Switch

 

 

 

 

 

erating mode setting switches 2, 3 and

 

doesn’t work

 

 

 

 

 

4 on the rear of the GT30 to ON and

 

(grid and

 

 

 

 

 

reset the power supply.

 

validity

 

 

CAUTION:

 

settings

 

 

When doing this, all of the contents will

 

noted above

 

 

revert to those in effect at the time of

 

are correct)

 

 

shipping, and all of the GT30 memory

 

 

 

 

contents will be cleared. Before doing

 

 

 

 

this, make sure all data has been

 

 

 

 

backed upage

 

 

 

 

 

 

141