Installing Server 3-5

Installation of Rack-mount Model

You can mount NEC Express5800/ft series on a rack that conforms to the EIA standards.

IMPORTANT: NEC Express5800/ft series is a precision instrument. You should ask maintenance personnel to install it.

To install a rack, contact your sales agent or maintenance personnel.

CAUTION

Do not attempt to install the server.

To avoid the risk of personal injury, users should not attempt to install the server into the rack assembly. The server should be installed in the rack only by trained maintenance personnel.

Room that can maintain the following conditions:

[When operating] Temperature: 10 to 35ºC* Humidity: 20 to 80% Temperature gradient: ±10ºC/hr Atmospheric pressure: 749 to 1040hpa [When not operating] Temperature: 5 to 40ºC*

Humidity: 10 to 80%

Temperature gradient: ±15ºC/hr

Atmospheric pressure: 749 to 1040hpa

100V - 120 V or 200V - 240 V parallel bi-polar power outlet with grounding

Wall outlet within the reach of supplied power cord.

Level and reinforced floor.

*It is recommended to use the server in a room where temperature can be kept between 15 and 25ºC.

Space 40 cm or more on top, 1 m or more on the front and rear, and 60 cm or more on the right and left.