Communications Errors

Chapter 6

 

 

 

 

 

 

 

 

Indicator

 

Display

Meaning

Countermeasures

 

 

 

 

 

 

 

 

 

 

 

Color

Status

 

 

 

 

 

 

 

 

 

 

 

WD

 

 

Green

Flashing

The CPU Unit of the Card is operating nor-

---

 

 

 

 

 

 

mally.

 

 

 

 

 

Red

Lit

The CPU Unit of the Card is not ready or

Check the Option Card con-

 

 

 

 

 

the CPU Unit has malfunctioned.

nector and turn ON the Invert-

 

 

 

 

 

 

er power supply.

 

 

 

 

 

 

Replace the Option Card.

 

 

 

 

 

 

 

 

 

 

 

---

Not lit

Power is not being supplied from the In-

Check the Option Card con-

 

 

 

 

 

verter.

nector and turn ON the Invert-

 

 

 

 

 

The Card is not connected properly and

er power supply.

 

 

 

 

 

 

 

 

 

 

 

 

power is not being to supplied to it.

Replace the Option Card.

 

 

 

 

 

 

 

Note

1. When both of the baud rate setting pins DR0 and DR1 are set to ON, both the MS and NS will

 

 

be lit in red.

 

 

 

Note

2. For communications line problems, detailed error codes will be displayed on the indicators of

 

 

the Master Unit. Check the error code and take appropriate countermeasures according to

 

 

the descriptions in Chapter 15 Troubleshooting and Maintenance of CompoBus/D (Device-

 

 

Net) Operation Manual (W267).

 

 